Overload Function; Ac Motor (18/19P6); Figure 1: Maximum Disconnecting Time Depending On The Load At Ac Motors; Figure 2: Output Current Depending Of Theoutput Frequency - KEB COMBIVERT P6 Instruction Manual

Hide thumbs Also See for COMBIVERT P6:
Table of Contents

Advertisement

Technical Data
3.1

Overload function

(from inverter firmware 2.2.0.43)
The permissible overload time is considerably depending on the cooling conditions. The over-
load protection of the inverter is triggered by the following reasons:
permissible heat sink temperature is exceeded => OH („Error! Overtemperature")
exceeding the disconnecting time in accordance with the characteristic above => OL („Er-
ror! Overload")
3.1.1

AC motor (18/19P6)

Overload function (OL)
Disconnecting time [min]
20
15
10
5
0
100
110
120
Figure 1:
Overload function in the lower speed range (OL2)
in the lower speed range the permissible output current is depending on the output frequency.
Depending on the setting of parameter is14 the error E.OL2 is triggerd or the output current
is limited on exceeding the output current.
Output current [A]
120 A
100 A
80 A
60 A
40 A
20 A
0 A
0
Figure 2:
18
130
140
150
160
170
Maximum disconnecting time depending on the load at AC motors
10
Output current depending of theoutput frequency
180
190
200
210
220
230
19P6, 2 kHz
18P6, 4 kHz
Output frequency [Hz]
20
Load [%]