System Design and Installation
For a simultaneous inrush for multiple Servo Drivers, select a no-fuse-breaker with a 20-ms allowable
current greater than the total inrush current shown in the following table for the applicable Servomotor
models.
Servo Driver
R88D-WTA3HL to -WT02HL
R88D-WTA3H to -WT04H
R88D-WT05H to -WT10H
R88D-WT15H
R88D-WT20H/-WT30H
R88D-WT50H
R88D-WT60H
D Surge Absorbers
Use surge absorbers to absorb surges from power supply input lines due to lightning, abnormal volt-
ages, etc. When selecting surge absorbers, take into account the varistor voltage, the amount of surge
immunity, and the amount of energy resistance. For 200-V AC systems, use surge absorbers with a
varistor voltage of 470 V. The surge absorbers shown in the following table are recommended.
Maker
Okaya Electric
y
I d
Industries Co., Ltd.
i
C
L d
Note 1.
Refer to the manufacturers' documentation for operating details.
Note
2. The surge immunity is for a standard impulse current of 8/20 µs. If pulses are wide, either decrease the
current or change to a larger-capacity surge absorber.
3-32
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Control-circuit power supply
30
35
60
60
60
60
65
Model
Max. limit
voltage
RSASV-781BYZ-2
783 V
RSASV-781BXZ-4
783 V
Inrush current (Ao-p)
Main-circuit power supply
90
90
130
130
140
140
140
Surge
Type
immunity
Block
1,000 A
Between power supply lines
1,000 A
Between power supply line
grounds
Chapter 3
Remarks