Binary Input Objects - YASKAWA BACnet/IP JOHB-SMP3 Technical Manual

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

7 BACnet/IP Objects Supported
Object ID
(Network Display, if Different)
Ext Drive 2 Freq Output
*4
AV55
(Ext Drive 2 Freq Out)
*4
AV56
Ext Drive 3 Freq Output
*4
AV57
(Ext Drive 3 Freq Out)
*4
AV58
Ext Drive 4 Freq Output
*4
AV59
(Ext Drive 4 Freq Out)
Ext Drive Register Write Access
*4
AV60
(Gateway Reg 0x15CE)
Ext Drive Write Register Number
*4
AV61
(Gateway Reg 0x15CF)
Ext Drive Write Register Data
*4
AV62
(Gateway Reg 0x15D0)
Ext Drive Register Read Access
*4
AV63
(Gateway Reg 0x15EF)
Ext Drive Read Register Number
*4
AV64
(Gateway Reg 0x15F0)
Ext Drive Read Register Data
*4
AV65
(Gateway Reg 0x15F1)
*1
Use with caution because bits 4 to A of AV1 will be logically ORed with the physical digital inputs. This can cause hard-wired
Normally Closed inputs to operate incorrectly.
*2
Available on bypasses only.
*3
Not available on all drives. Refer to the Technical Manual of your drive, and check if the Modbus register of the applicable object
exists.
*4
See Gateway Mode features in drive manuals for use instructions of AV43-AV65. Not visible when connected to a drive that does not
support Gateway Mode.

Binary Input Objects

Object ID
(Network Display, if Different)
Drive Input Terminal 1
BI1
Drive Input Terminal 2
BI2
Drive Input Terminal 3
BI3
Drive Input Terminal 4
BI4
Drive Input Terminal 5
BI5
Drive Input Terminal 6
BI6
Drive Input Terminal 7
BI7
BI8
(Multi Function Out 1)
BI9
(Multi Function Out 2)
BI10
(Multi Function Out 3)
BYP DI-1 STAT for bypass
Drive Input Terminal 8
BI11
BYP DI-2 STAT for bypass
*1
BI12
*1
BI13
28
Object Name
Modbus Register (Hex.)
Ext Drive 3 Status
Ext Drive 4 Status
Object Name
Modbus Register (Hex.)
(Input Terminal 1)
(Input Terminal 2)
(Input Terminal 3)
(Input Terminal 4)
(Input Terminal 5)
(Input Terminal 6)
(Input Terminal 7)
Drive MF Output 1
Drive MF Output 2
Drive MF Output 3
8781 for bypass: Bit 0
(Input Terminal 8)
8781 for bypass: Bit 1
BYP DI-3 STAT
BYP DI-4 STAT
Range
15EA
0 - 65535
15EB
0 - 65535
15EC
0 - 65535
15ED
0 - 65535
15EE
0 - 65535
15CE
0 - 65535
15CF
0 - 65535
15D0
0 - 65535
15EF
0 - 65535
15F0
0 - 65535
15F1
0 - 65535
Active Text
002B: Bit 0
ON
002B: Bit 1
ON
002B: Bit 2
ON
002B: Bit 3
ON
002B: Bit 4
ON
002B: Bit 5
ON
002B: Bit 6
ON
0020: Bit 5
ON
0020: Bit 6
ON
0020: Bit 7
ON
002B: Bit 7
ON
8781: Bit 2
ON
8781: Bit 3
ON
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Unit
PV Access
-
R
-
R
-
R
-
R
-
R
-
W
-
W
-
W
-
R
-
R
-
R
Inactive Text
PV Access
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R