Procedure C - YASKAWA BACnet/IP JOHB-SMP3 Technical Manual

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

4.
Remove the screw (D) installed in the drive grounding terminal (A).
5.
Use the screw (C) installed in the FE ground terminal of the drive (A) to connect one end of the included
ground wire (H) to the ground terminal on the drive.
Route ground wire on the right side of the stud (K).
Tighten the screw to a correct tightening torque:
• 0.5 N∙m to 0.6 N∙m (4.4 lbf∙in to 5.3 lbf∙in)
6.
Install the option (B) into the CN5 connector (M) (HV600: CN5, FP605: CN5-A) on the drive and use one
of the included screws (C) to put it in place.
Tighten the screw to a correct tightening torque:
• 0.5 N∙m to 0.6 N∙m (4.4 lbf∙in to 5.3 lbf∙in)
Note:
Only two screws are necessary to install the option on HV600 and FP605 drives.
7.
Use one of the remaining included screws (C) to connect the ground wire (H) to the ground terminal and
installation hole on the option (B).
Refer to
Figure 5.5
Tighten the screw to a correct tightening torque:
• 0.5 N∙m to 0.6 N∙m (4.4 lbf∙in to 5.3 lbf∙in)
8.
Firmly connect the Ethernet communication cables to CN1B (Port 2) (I), and/or CN1A (Port 1) (J).
Isolate communication cables from main circuit wiring and other electrical and power lines. Make sure that
you firmly connect the cable end. Refer to
information.
9.
Reattach the drive front cover (E) and the keypad (F).
Refer to the drive manuals for more information.
NOTICE
erroneous operation.
10.
Set drive parameters in

Procedure C

This section shows the procedure to install and wire the option on an HV600 Bypass.
Install the Option
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
NOTICE
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic
discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry.
1.
Remove the HV600 Bypass cover.
2.
Put the option into port CN5 on the bypass PCB.
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
for instruction about crimp terminal orientation and wire routing.
Do not pinch cables between the front covers and the drive. Failure to comply could cause
Related Drive Parameters on page 18
Communication Cable Specifications on page 17
for correct option performance.
5 Installation Procedure