YASKAWA AC Drive Option BACnet/IP Technical Manual Model JOHB-SMP3 To correctly use the product, read this manual thoroughly and keep it for easy reference, inspection, and maintenance. Make sure that the end user receives this manual. MANUAL NO. SIEP C730600 0MA...
YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • Contact Yaskawa or a Yaskawa representative and provide the manual number shown on the front cover to order new copies of the manual. DANGER Do not ignore the safety messages in this manual.
• Make sure that there is no damage to the option and no parts are missing. The Yaskawa warranty does not include damage from shipping. If there is damage to the option or other parts, contact the shipping company immediately.
Connect the included ground wire during installation. ◆ Communication Connector Option connections CN1A (Port 1) and CN1B (Port 2) are connection points for customer-supplied BACnet/IP network communication cables. These ports accept customer-supplied male 8-way ethernet modular RJ45 connectors. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Green Flashing BACnet/IP command(s) received command in the last 2 seconds. This also includes gateway drive commands. Communications error (fatal) The option detected a duplicate IP address. 10/100 Green 10 Mbps is established YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Do not operate a drive or connected equipment that has damaged or missing parts. You can cause damage to the drive and connected equipment. NOTICE Use Yaskawa connection cables or recommended cables only. Incorrect cables can cause the drive or option to function incorrectly. NOTICE Damage to Equipment.
Prepare the Drive for the Option Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions correctly. Refer to the drive manuals for more information. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 12
To prevent damage to the cable from the cut end, treat the cut surface with sandpaper. • Route the option wiring inside the enclosure as shown in Figure 5.4-B. Refer to the drive manuals for more information. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Prepare the Drive for the Option Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions correctly. Refer to the drive manuals for more information. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 14
Make sure that the charge indicator LED is unlit, then remove the keypad and front cover. Refer to the drive manuals for more information. Remove the keypad (F) and front cover (E). Put the LED label (G) in the correct position on the drive front cover (E). YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
(ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry. Remove the HV600 Bypass cover. Put the option into port CN5 on the bypass PCB. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 16
Make sure that you did not pinch cables between the front cover and the bypass enclosure, then replace and secure the front cover. Set drive parameters in Related Drive Parameters on page 18 for correct option performance. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
5 Installation Procedure ◆ Communication Cable Specifications Yaskawa recommends using shielded Cat5e cable or better. The Yaskawa warranty does not cover other cable types. ■ Option Connection Diagram Figure 5.8 Option Connection Diagram Connect the specified ground wire. ■ Communication Topology Specifications Drives equipped with the JOHB-SMP3 option can be connected to network in either star or line topology.
Selects whether communication-related parameters F6-xx and F7-xx are set back to original @Initialize default values when you use parameter A1-03 [Initialize Parameters] to initialize the drive. (036A) (0, 1) 0 : No Reset - Parameters Retained 1 : Reset - Back to Factory Default YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 19
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables communication OPT parameter changes without turning on the power again. F7-05 Subnet Mask 1 Sets the static/fixed Subnet Mask. Sets the most significant octet. (03E9) (0 - 255) YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 21
It is not necessary to cycle power on the drive. (0502) (0 - 3) 0 : 0.01 Hz units 1 : 0.01% units 2 : min (r/min) units 3 : User Units (o1-09 -o1-11) YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 22
• 76 to 7F = Other switch positions that are incorrect for BACnet/IP Note: • Not all drive software versions will display this monitor. Contact Yaskawa or your nearest sales representative for more information. • This monitor is not available in Z1000U drives.
When using AV4, do not use BO1 to BO3 or BV12. Drive Reference Select Command (Reference Select Cmd) 000F 0 - 32767 Bitmap • Bit 0: Reserved • Bit 1: PID Setpoint Input YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Drive Input Terminal 8 002B: Bit 7 BI11 (Input Terminal 8) 8781 for bypass: Bit 1 BYP DI-2 STAT for bypass BI12 BYP DI-3 STAT 8781: Bit 2 BI13 BYP DI-4 STAT 8781: Bit 3 YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
◆ Binary Value Objects Object Name Object ID Modbus Register (Hex.) Active Text Inactive Text PV Access (Network Display, if Different) Run FWD Cmd 0001: Bit 0 Run REV Cmd 0001: Bit 1 YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 30
002C: Bit 2 Desired Frequency Agree BV36 002C: Bit 3 (Desired Freq Agree) BV37 Frequency Detect 1 002C: Bit 4 BV38 Frequency Detect 2 002C: Bit 5 BV39 Drive Startup Complete 002C: Bit 6 YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 31
(BYP DI-08 Command) Bypass HAND Mode Status BV80 8784: Bit 0 (BYP HAND Mode Status) Bypass OFF Mode Status BV81 8784: Bit 1 (BYP OFF Mode Status) BV82 Bypass AUTO Mode Status 8784: Bit 2 YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 32
Bypass only. Command a drive forward run or a bypass run. Bypass only. Command a drive reverse run. Not available on Z1000U. Available on HV600 and HV600 Bypass drives. Set b1-04 = 0 to use. Available on bypass only. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Type: “OBJECT_DEVICE” (fixed) Object List <List of all available objects> Settable via the network. If not set, it will default to: “Yaskawa” + “VFD” or BYP” + “ID” + F6-49 (Hex.) + F6-48 (Hex.) Object Name Example: “Yaskawa VFD ID092A5A”...
The JOHB-SMP3 IP Address is available using drive keypad to access Option Monitors U6-80 to U6-83. Refer to Table 6.1 for more information. ◆ Home Page The Home page shows the status of the drive and the I/O. It also shows identifying information about the drive and the option. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Cumulative number of messages dropped due to input network buffer being full and unable to hold the new message. Msg Rx Errors Cumulative number of receive errors reported by the MAC/PHY (Media Access Control/Physical Layer). YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
• Output Current • Motor Speed • Torque Reference • DC Bus Voltage • Terminal Analog Input 1 • Terminal Analog Input 2 • Terminal Analog Input 3 Figure 8.4 Chart Page View YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Enter the message that will appear in the email contents. Enter the email subject. ◆ Parameter Access Page (Requires Security Login) The Parameter Access page lets you read parameters, monitors and other Memobus registers from the drive. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Entering a valid password allows access to the settings in the Settings page, Email Alerts page, and the Parameter Access page. ■ Webpage Password To change the password, enter the new password in the “New Password:” and “Confirm Password:” text boxes. Click “Save password”. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
To use other options, refer to those option manuals. Invalid DIP switch S1 setting. Set the option DIP switch S1 as shown in page 11. Monitor, U4- 75 [Communication OPT Protocol] will display the DIP switch S1 setting. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
[Option Communication Error] fault. To disable BACnet/IP Timeout detection, set F7-57 = 0. When this parameter is set to 0, a periodic command from the BACnet/IP controller is not necessary. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
1103 Factory default MAC Address programmed into the option. Note: Return the option to Yaskawa or your nearest sales representative and request the setting change. Network Link Down 1104 Neither of the two network Ethernet ports has a link. This will only happen when a link is established, then lost.
Verify the following installation conditions to make sure that other devices and machinery used with this option and drive also comply with EMC Directive: Use dedicated shielded cable for the option and external device (encoder, I/O device, IO-Controller), or run the wiring through a metal conduit. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 44
Figure 10.3 Option Installation for CE Compliance: HV600 Figure 10.4 Option Installation for CE Compliance: FP605 Ground the largest possible surface area of the shield to the metal panel. Yaskawa recommends using cable clamps. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
-10 °C to +50 °C (14 °F to +122 °F) Humidity Up to 95% RH (no condensation) Storage Temperature -20 °C to +60 °C (-4 °F to +140 °F) allowed for short-term transport of the product YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
The Yaskawa SMP3 BACnet/IP option kit provides BACnet communications for Yaskawa AC drives. The Yaskawa BACnet/IP feature connects the Yaskawa AC drives to a standard BACnet/IP network. These products may be fully controlled and monitored over BACnet. All drive parameters are available for reading and writing.
Page 47
Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ■ ISO 10646 (UTF-8) □ IBM/Microsoft DBCS □ ISO 8859-1 □ ISO 10646 (UCS-2) □ ISO 10646 (UCS-4) □ JIS X 0208 YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
The wheelie bin symbol on this product, its manual, or its packaging identifies that you must recycle it at the end of its product life. You must discard the product at an applicable collection point for electrical and electronic equipment (EEE). Do not discard the product with usual waste. YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Revision History Date of Publication Revision Number Section Revised Content October 2022 First Edition YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual...
Page 50
Phone: +81-3-5402-4502 Fax: +81-3-5402-4580 www.yaskawa.co.jp YASKAWA AMERICA, INC. 2121, Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: +1-800-YASKAWA (927-5292) or +1-847-887-7000 Fax: +1-847-887-7310 www.yaskawa.com YASKAWA ELÉTRICO DO BRASIL LTDA. 777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil Phone: +55-11-3585-1100 Fax: +55-11-3585-1187 www.yaskawa.com.br...