7 BACnet/IP Objects Supported
Object ID
(Network Display, if Different)
• Bit 2: Reserved
• Bit 3: Reserved
• Bit 4: PI2 Target Input
• Bit 5 to B: Reserved
• Bit C: Multi-Function Input 5
• Bit D: Multi-Function Input 6
• Bit E: Multi-Function Input 7
• Bit F: Reserved
Note:
When you use AV5, you must not use
AV1, BO4, or BV9 to BV11.
System Status
• Bit 0: During Run (drive or bypass)
• Bit 1: During Reverse
• Bit 2: System Ready
• Bit 3: System Faulted
• Bit 4: Data Setting Error
• Bit 5: Multi-Function Digital Output 1
(terminal M1-M2)
AV6
• Bit 6: Multi-FunctionDigital Output 2
(terminal M5-M6)
• Bit 7: Multi-FunctionDigital Output 3
(terminal M5-M6)
(Z1000U: MD-ME-MF)
• Bit 8 to D: Reserved
• Bit E: ComRef status
• Bit F: ComCtrl status
Fault Details
• Bit 0: oC [Overcurrent], GF [Ground
Fault]
• Bit 1: ov [Overvoltage]
• Bit 2: oL2 [Drive Overload]
• Bit 3: oH1 [Heatsink Overheat], oH2
[External Overheat (H1-XX=B)]
• Bit 4 to 6: Reserved
• Bit 7: EF to EF7 [External Fault]
• Bit 8: CPFxx [Hardware Fault]
(includes oFAxx)
• Bit 9: oL1 [Motor Overload], oL3
AV7
[Overtorque Detection 1], UL3
[Undertorque Detection 1]
• Bit A: Reserved
• Bit B: Uv [Undervoltage]
• Bit C: Uv1 [DC Bus Undervoltage],
Uv2 [Control Power Undervoltage],
Uv3 [Soft Charge Answerback Fault]
• Bit D: LF [Output Phase Loss], PF
[Input Phase Loss]
• Bit E: CE [Modbus Communication
Error], bUS [Option Communication
Error]
• Bit F: oPr [Keypad Connection Fault]
Data Link Status
• Bit 0: Writing Data
• Bit 1: Reserved
• Bit 2: Reserved
AV8
• Bit 3: Upper or lower limit error
• Bit 4: Data conformity error
• Bit 5: Writing to EEPROM
• Bit 6 to F: Reserved
AV9
Frequency Reference
AV10
AV11
AV12
AV13
*3
AV14
Drive Multi-Function Input Status
AV15
AV16
26
Object Name
Modbus Register (Hex.)
Output Frequency
Output Voltage
Output Current
Output Power
Torque Reference
(MF Input Status)
Drive Status 2
Range
0020
0 - 65535
0021
0 - 65535
0022
0 - 63
0040
0 - 600.00
0041
0 - 600.00
0045
0 - 6553.5
0026
0 - 6553.5
0 - 6553.5 > 11 kVA
0047
0 - 655.35 ≤ 11 kVA
0048
0 - 100.0
002B
0 - 255
002C
0 - 65535
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Unit
PV Access
Bitmap
R
Bitmap
R
Bitmap
R
Determined by o1-03
R
Determined by o1-03
R
V
R
A
R
KW
R
%
R
Bitmap
R
Bitmap
R

Advertisement