7 BACnet/IP Objects Supported
Object ID
(Network Display, if Different)
BV3
BV4
Drive Com Net Command
BV5
Drive Com Control Command
BV6
(Com Control Cmd)
Drive Multi-Function Input 3 Command
*3
BV7
*3
BV8
Drive Multi-Function Input 4 Command
Drive Multi-Function Input 5 Command
*3
BV9
Drive Multi-Function Input 6 Command
*3
BV10
Drive Multi-Function Input 7 Command
*3
BV11
Set Fault Contact Cmd
BV12
(Set Flt Contact Cmd)
BV13
BV14
BV15
BV16
BV17
Overcurrent – Ground Fault
BV18
(Overcurrent– Gnd Flt)
Main Circuit Overvoltage
BV19
(Main Ckt Overvoltage)
BV20
BV21
BV22
BV23
BV24
BV25
Motor Overload – Overtorque
BV26
(Mtr OvrLd – OvrTorque)
BV27
Main Circuit Undervoltage
BV28
(Main Ckt Undrvoltage)
MCU, Control Power Supply Error
BV29
(MCU Cntrl Pwr Sy Err)
BV30
BV31
BV32
Operator Disconnect
BV33
BV34
BV35
Desired Frequency Agree
BV36
(Desired Freq Agree)
BV37
BV38
BV39
Drive Startup Complete
30
Object Name
Modbus Register (Hex.)
Drive EF0
(Ext Fault Cmd)
Drive Fault Reset
(Fault Reset Cmd)
(Com Net Cmd)
(MF Input 3 Cmd)
(MF Input 5 Cmd)
(MF Input 6 Cmd)
(MF Input 7 Cmd)
RUN-STOP
REV-FWD
READY
FAULT
Data Set Error
Drive Overload
Drive Overheat
Fuse Blown
PI Feedback Loss
External Fault
Hardware Error
Overspeed
Output Phase Loss
BUS Fault
Operating
Zero Speed
Frequency Agree
Frequency Detect 1
Frequency Detect 2
Active Text
0001: Bit 2
FAULT
0001: Bit 3
RESET
-
COM
-
COM
0001: Bit 6
ON
0001: Bit 7
ON
0001: Bit 8
ON
0001: Bit 9
ON
0001: Bit A
ON
0009: Bit 6&7
ENABLE
0020: Bit 0
RUN
0020: Bit 1
REV
004B: Bit 5
READY
0020: Bit 3
FAULTED
004B: Bit 8
ERROR
OC – GF
0021: Bit 0
0021: Bit 1
OV
0021: Bit 2
OL2
0021: Bit 3
OH1-OH2
0021: Bit 5
PUF
0021: Bit 6
FBL
0021: Bit 7
EF0 – EF
0021: Bit 8
CPF
OL1 – OL3
0021: Bit 9
OS –DEV
0021: Bit A
0021: Bit B
UV
0021: Bit C
UV1-2-3
0021: Bit D
LF
0021: Bit E
BUS
0021: Bit F
OPR
002C: Bit 0
OPERATING
002C: Bit 1
ON
002C: Bit 2
ON
002C: Bit 3
ON
002C: Bit 4
ON
002C: Bit 5
ON
002C: Bit 6
ON
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Inactive Text
PV Access
OFF
C
OFF
C
LOCAL
C
LOCAL
C
OFF
C
OFF
C
OFF
C
OFF
C
OFF
C
OFF
C
OFF
R
FWD
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R

Advertisement