No.
Name
(Hex.)
F6-14
Bus Error Auto Reset
(03BB)
F6-15
Comm. Option Parameters
Reload
(0B5B)
F6-16
Gateway Mode
(0B8A)
F6-48
BACnet Device Object
Identifier 0
(02FE)
F6-49
BACnet Device Object
Identifier 1
(02FF)
F7-01
IP Address 1
(03E5)
F7-02
IP Address 2
(03E6)
F7-03
IP Address 3
(03E7)
F7-04
IP Address 4
(03E8)
F7-05
Subnet Mask 1
(03E9)
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Note:
When you set F6-08 to 1 and you then use A1-03 to initialize the drive, the drive will not
change this setting value.
Sets the automatic reset function for bUS [Option Communication Error].
0 : Disabled
1 : Enabled
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Sets when the drive will activate the F6-xx/F7-xx communications-related parameters that you
changed. Use this parameter as an alternative to cycling power to the drive to active parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
Note:
• F6-15 is reset to 0 after setting 1 or 2.
• This parameter is not available in Z1000U drive.
• Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
Sets the gateway mode operation and the number of connected slave drives..
0 : Disabled
1 : Enabled: 1 Slave Drive
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
Note:
This parameter is not available in Z1000U drive.
Sets the Instance Identifier of the BACnet Device Object, where the F6-48 value is the least
significant word.
Note:
This parameter and F6-49 set the Instance Identifier of the BACnet Device Object.
Example 1: Set the Device Object Instance Identifier to 1234. 1234 decimal is equal to 4D2
(Hex.). Set F6-48 = 4D2 (Hex.) and F6-49 = 0 (Hex.).
Example 2: Set the Device Object Instance Identifier to 1234567. 1234567 decimal is equal to
12D687 (Hex.). Set F6-48 = D687 (Hex.) and F6-49 = 12 (Hex.).
Sets the Instance Identifier of the BACnet Device Object, where the F6-49 value is the most
significant word.
Note:
This parameter and F6-48 set the Instance Identifier of the BACnet Device Object.
Example 1: Set the Device Object Instance Identifier to 1234. 1234 decimal is equal to 4D2
(Hex.). Set F6-48 = 4D2 (Hex.) and F6-49 = 0 (Hex.).
Example 2: Set the Device Object Instance Identifier to 1234567. 1234567 decimal is equal to
12D687 (Hex.). Set F6-48 = D687 (Hex.) and F6-49 = 12 (Hex.).
Sets the static/fixed IP address. Sets the most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables
communication OPT parameter changes without turning on the power again.
Sets the static/fixed IP address. Sets the second most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables
communication OPT parameter changes without turning on the power again.
Sets the static/fixed IP address. Sets the third most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables
communication OPT parameter changes without turning on the power again.
Sets the static/fixed IP address. Sets the fourth most significant octet.
Note:
• This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static].
• All IP Addresses must be unique.
• You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables
communication OPT parameter changes without turning on the power again.
Sets the static/fixed Subnet Mask. Sets the most significant octet.
Description
6 Related Drive Parameters
Default
(Range)
0
(0, 1)
0
(0 - 2)
0
(0 - 4)
1
(0 - FFFF (Hex.))
0
(0 - 3F (Hex.))
192
(0 - 255)
168
(0 - 255)
1
(0 - 255)
20
(0 - 255)
255
(0 - 255)
19