YASKAWA BACnet/IP JOHB-SMP3 Technical Manual page 22

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

6 Related Drive Parameters
No.
Name
Communication OPT
U4-75
Protocol
U4-76 - U4-78
MAC Address 1
U4-79 - U4-81
MAC Address 2
Expert
U4-82 - U4-84
MAC Address 3
Expert
U6-80 - U6-83
Option IP Address 1 - 4
U6-84 - U6-87
Online Subnet 1 - 4
U6-88 - U6-91
Online Gateway 1 - 4
U6-92
Online Speed
U6-93
Online Duplex
U6-94
OPT SPARE 1
22
Table 6.1 Option Monitor
Shows the setting of DIP switch S1.
• 70 = All switches OFF (incorrect for BACnet/IP)
• 71 to 74 = Incorrect for BACnet/IP
• 75 = Switches 1 and 3 ON, all other OFF (correct for BACnet/IP)
• 76 to 7F = Other switch positions that are incorrect for BACnet/IP
Note:
• Not all drive software versions will display this monitor. Contact Yaskawa or your nearest
sales representative for more information.
• This monitor is not available in Z1000U drives.
Shows the Main MAC Address.
• U4-76: First octet, Second octet
• U4-77: Third octet, Fourth octet
• U4-78: Fifth octet, Sixth octet
Note:
• Not all drive software versions will display this monitor. Contact Yaskawa or your nearest
sales representative for more information.
• This monitor is not available in Z1000U drives.
Shows the second MAC Address.
• U4-79: First octet, Second octet
• U4-80: Third octet, Fourth octet
• U4-81: Fifth octet, Sixth octet
Note:
• Not all drive software versions will display this monitor. Contact Yaskawa or your nearest
sales representative for more information.
• This monitor is not available in Z1000U drives.
Shows the third MAC Address.
• U4-82: First octet, Second octet
• U4-83: Third octet, Fourth octet
• U4-84: Fifth octet, Sixth octet
Note:
• Not all drive software versions will display this monitor. Contact Yaskawa or your nearest
sales representative for more information.
• This monitor is not available in Z1000U drives.
Shows the currently available local IP Address.
• U6-80: First octet
• U6-81: Second octet
• U6-82: Third octet
• U6-83: Fourth octet
Shows the currently available subnet mask.
• U6-84: First octet
• U6-85: Second octet
• U6-86: Third octet
• U6-87: Fourth octet
Shows the currently available gateway address.
• U6-88: First octet
• U6-89: Second octet
• U6-90: Third octet
• U6-91: Fourth octet
Shows CN1A Port 1 link speed.
Shows CN1A Port 1 duplex setting.
Shows CN1B Port 2 link speed.
Description
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Range
00 - FF (Hex.)
0000 - FFFF (Hex.)
0000 - FFFF (Hex.)
0000 - FFFF (Hex.)
0 - 255
0 - 255
0 - 255
10: 10 Mbps
100: 100 Mbps
0: Half/Half
1: Full/Full
10: 10 Mbps

Advertisement

Table of Contents
loading

Table of Contents