Option Led States - YASKAWA BACnet/IP JOHB-SMP3 Technical Manual

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

Table 4.1 Male 8-way Ethernet Modular Connector (Customer-Supplied)
Male 8-way Ethernet Modular Connector

Option LED States

The option has four LEDs:
• Bi-color Status LEDs:
– Module status (MS) red/green
– Network status (NS) red/green
• Ethernet Port LEDs (2 each):
– Network speed-10/100 green
– Link status and network activity-Link/Act green
A - Z1000U
B - Not applicable
*1
LED label has transparent background and white letters. Please make sure that you use the correct label for HV600.
Wait 2 seconds minimum for the power-up diagnostic process to complete before you verify the LED states. The
Table 4.2
shows the operating status of the option LEDs after the power-up diagnostic LED sequence is complete.
Refer to
Table 4.3
for more information about the LEDs.
LED Name
MS
NS
*1
10/100
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Figure 4.2 Option LED Labels
Table 4.2 Option LED States
Indication
Color
Display
-
OFF
Green
ON
Green
Flashing
Red
ON
Red
Flashing
-
OFF
Green
ON
Green
Flashing
Red
ON
Green
OFF
Pin
1 (Pair 2)
2 (Pair 2)
3 (Pair 3)
4 (Pair 1)
5 (Pair 1)
6 (Pair 3)
7 (Pair 4)
8 (Pair 4)
C - HV600, FP605
*1
Operating State
Power supply off
Option operating
Option initializing
Fatal error occurred
Non-fatal error occurred
Power supply OFF or no BACnet/IP traffic
BACnet/IP message(s) received
BACnet/IP command(s) received
Communications error (fatal)
10 Mbps is established
4 Option Components
Description
Transmit data (TXD) +
Transmit data (TXD) -
Receive data (RXD) +
Not used
Not used
Receive data (RXD) -
Not used
Not used
Description
There is no power to the drive.
The option is operating normally.
The option is configuring an IP address.
The option detected a fatal (unrecoverable)
error.
The option detected a non-fatal
(recoverable) error.
The option has not received a BACnet/IP
message or command for 2 seconds or
longer.
The option received at least one BACnet/
IP message in the last 2 seconds.
The option received at least one Frequency
Reference or Run/Stop BACnet/IP
command in the last 2 seconds. This also
includes gateway drive commands.
The option detected a duplicate IP address.
-
9

Advertisement

Table of Contents
loading

Table of Contents