13 BACnet Protocol Implementation Conformance Statement

Items
Area of Use
Altitude
13
BACnet Protocol Implementation Conformance
Statement
• Date: 05/01/2021
• Vendor Name: Yaskawa
• Product Name: AC Motor Controller
• Product Model Number: JOHB-SMP3
• Application Software Version: VST9070xx
• Firmware Revision: 3.x
• BACnet Protocol Revision: 19
• Product Description:
The Yaskawa SMP3 BACnet/IP option kit provides BACnet communications for Yaskawa AC drives. The
Yaskawa BACnet/IP feature connects the Yaskawa AC drives to a standard BACnet/IP network. These products
may be fully controlled and monitored over BACnet. All drive parameters are available for reading and writing.
• BACnet Standardized Device Profile (Annex L):
□ BACnet Cross-Domain Advanced Operator Workstation (B-XAWS)
□ BACnet Advanced Operator Workstation (B-AWS)
□ BACnet Operator Workstation (B-OWS)
□ BACnet Operator Display (B-OD)
□ BACnet Advanced Life Safety Workstation (B-ALSWS)
□ BACnet Life Safety Workstation (B-LSWS)
□ BACnet Life Safety Annunciator Panel (B-LSAP)
□ BACnet Advanced Access Control Workstation (B-AACWS)
□ BACnet Access Control Workstation (B-ACWS)
□ BACnet Access Control Security Display (B-ACSD)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
■ BACnet Application Specific Controller (B-ASC)
□ BACnet Smart Actuator (B-SA)
□ BACnet Smart Sensor (B-SS)
□ BACnet Advanced Life Safety Controller (B-ALSC)
□ BACnet Life Safety Controller (B-LSC)
□ BACnet Advanced Access Control Controller (B-AACC)
□ BACnet Access Control Controller (B-ACC)
□ BACnet Router (B-RTR)
□ BACnet Gateway (B-GW)
□ BACnet Broadcast Management Device (B-BBMD)
□ BACnet Access Control Door Controller (B-ACDC)
□ BACnet Access Control Credential Reader (B-ACCR)
□ BACnet General (B-GENERAL)
• List all BACnet Interoperability Building Blocks Supported (Annex K):
– Data Sharing-ReadProperty-B (DS-RP-B)
– Data Sharing-WriteProperty-B (DS-WP-B)
– Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
– Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
– Data Sharing-Change Of Value-B (DS-COV-B)
– Data Sharing-Change Of Value Property-B (DS-COVP-B)
46
Indoors and free from:
• Oil mist, corrosive gas, flammable gas, and dust
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
• Falling foreign objects
Up to 1000 m (3281 ft)
Note:
You can use the option at a maximum of 4000 m (13123 ft), depending on the model of the drive and the operating
conditions. Refer to the drive manuals for more information.
Specifications
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual

Advertisement

Table of Contents
loading

Table of Contents