YASKAWA BACnet/IP JOHB-SMP3 Technical Manual page 21

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

No.
Name
(Hex.)
F7-15
Communication Speed
Selection
(03F3)
F7-50
BACnet/IP Port
(1BC1)
F7-51
BBMD Foreign Register
Addr 1
(1BE9)
F7-52
BBMD Foreign Register
Addr 2
(1BEA)
F7-53
BBMD Foreign Register
Addr 3
(1BEB)
F7-54
BBMD Foreign Register
Addr 4
(1BEC)
F7-55
BBMD Foreign Port #
(1BED)
F7-56
BBMD Foreign Register
Time
(1BEE)
F7-57
BACnet/IP BUS Timeout
Value
(1BEF)
H5-11
Communications ENTER
Function Selection
(043C)
(Function common to
communication option)
o1-03
Frequency Display Unit
Selection
(0502)
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Note:
You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables communication
OPT parameter changes without turning on the power again.
Sets the communications speed (Port 1 (CN1A)/Port 2 (CN1B)).
10 : 10/10 Mbps (10 Mbps/10 Mbps)
100 : 100/100 Mbps (100 Mbps/100 Mbps)
101 : [Not Used/No function] 10/100 Mbps (10 Mbps/100 Mbps)
102 : [Not Used/No function] 100/10 Mbps (100 Mbps/10 Mbps)
Note:
• F7-15 is only effective when the port is set to half or full duplex in F7-14 [Duplex Mode
Selection].
• You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting F6-15 = 1 [Comm. Option Parameters Reload = Reload Now] enables
communication OPT parameter changes without turning on the power again.
Sets the UDP port on which the drive will receive incoming BACnet messages.
Sets the first octet of the IP Address of the BACnet Broadcast Management Device (BBMD) to
which the drive will register as a foreign device.
Sets the second octet of the IP Address of the BACnet Broadcast Management Device (BBMD) to
which the drive will register as a foreign device.
Sets the third octet of the IP Address of the BACnet Broadcast Management Device (BBMD) to
which the drive will register as a foreign device.
Sets the fourth octet of the IP Address of the BACnet Broadcast Management Device (BBMD) to
which the drive will register as a foreign device.
Sets the UDP port of the BBMD device to which the drive will register.
Sets the time interval in which the drive will repeat BBMD foreign registration.
Sets the length of time that the drive will wait after it receives a Run command or frequency
reference command before it detects a bUS fault.
Sets when an Enter command is necessary to use MEMOBUS/Modbus communications to change
parameter values.
0 : Parameter changes are activated when ENTER command is written
1 : Parameter changes are activated immediately. No ENTER command is necessary.
Sets the display units for the frequency reference and output frequency. Changes to this parameter
take effect immediately. It is not necessary to cycle power on the drive.
0 : 0.01 Hz units
1 : 0.01% units
2 : min
-1
(r/min) units
3 : User Units (o1-09 -o1-11)
Description
6 Related Drive Parameters
Default
(Range)
10
(10 - 102)
47808
(1024 - 65535)
0
(0 - 255)
0
(0 - 255)
0
(0 - 255)
0
(0 - 255)
47808
(1024 - 65535)
3600 s
(0 - 65535 s)
3600 s
(0 - 65535 s)
0
(0, 1)
0
(0 - 3)
21