YASKAWA BACnet/IP JOHB-SMP3 Technical Manual page 32

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

7 BACnet/IP Objects Supported
Object ID
(Network Display, if Different)
(BYP AUTO Mode Status)
Bypass DRIVE Mode Status
*8
BV83
(BYP DRV Mode Status)
Bypass BYPASS Mode Status
*8
BV84
(BYP BYPASS Mode Stat)
Bypass Emergency Run Bypass Status
*8
BV85
(BYP Em-Over BYP Stat)
Bypass Emergency Run Drive Fwd
*8
BV86
(BYP Em-Over DRV Stat)
Bypass Safety Status
*8
BV87
Bypass BAS Interlock Status
*8
BV88
(BYP BAS Interlk Stat)
*8
BV89
*8
BV90
Bypass Auto Transfer Status
*8
BV91
(BYP Auto Xfer Status)
Bypass Remote Transfer Status
*8
BV92
(BYP Remote Xfer Stat)
Bypass Energy Savings Status
*8
BV93
(BYP Energy Save Stat)
Bypass Motor 1 Select Status
*8
BV94
(BYP Motor 1 Sel Stat)
Bypass Motor 2 Select Status
*8
BV95
(BYP Motor 2 Sel Stat)
Bypass Drive Fault Status
*8
BV96
(BYP Drive Flt Status)
BYP Safety Status 2
*8
BV97
(BYP Safety Status 2)
Bypass BAS Interlock Fault Status
*8
BV98
(BYP BAS ILock Status)
Bypass External Fault Status
*8
BV99
(BYP Ext Fault Stat)
Bypass Motor OL Status
*8
BV101
(BYP Motor OL Stat)
Bypass Motor 1 External OL Status
*8
BV102
(BYP Motor 1 OL Stat)
Bypass Motor 2 External OL Status
*8
BV103
(BYP Mtr 2 OL Stat)
Bypass Brownout Detect Status
*8
BV104
(BYP Brownout Detect)
Bypass Drive Comms Status
*8
BV105
(BYP Drive Comms)
Bypass Loss of Load Status
*8
BV106
(BYP Loss Of Load)
Option Board on Drive Status
*8
BV107
(BYP Option Brd Comms)
*1
Drive only. For bypass, use BV58.
*2
Drive only. For bypass, use BV59.
*3
Use with caution because objects BV7 to BV11 will be logically ORed with the physical digital inputs. This can cause hard-wired
Normally Closed inputs to operate incorrectly.
*4
Bypass only. Command a drive forward run or a bypass run.
*5
Bypass only. Command a drive reverse run.
*6
Not available on Z1000U. Available on HV600 and HV600 Bypass drives.
*7
Set b1-04 = 0 to use.
*8
Available on bypass only.
32
Object Name
Modbus Register (Hex.)
Status
(BYP Safety Status)
Bypass Run Status
(BYP RUN Status)
Bypass Fault Status
(BYP Fault Status)
Active Text
8784: Bit 3
ON
8784: Bit 4
ON
8784: Bit 5
ACTIVE
8784: Bit 6
ACTIVE
8784: Bit 7
OPEN
8785: Bit 0
OPEN
8785: Bit 1
RUN
8785: Bit 2
FAULT
8785: Bit 3
ACTIVE
8785: Bit 4
ACTIVE
8785: Bit 5
ACTIVE
8785: Bit 6
SELECT
8785: Bit 7
SELECT
8786: Bit 0
FAULT
8786: Bit 1
OPEN
8786: Bit 2
FAULT
8786: Bit 3
FAULT
8786: Bit 5
FAULT
8786: Bit 6
FAULT
8786: Bit 7
FAULT
8787: Bit 0
FAULT
8787: Bit 2
FAULT
8787: Bit 5
FAULT
8787: Bit 4
FAULT
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Inactive Text
PV Access
OFF
R
OFF
R
OFF
R
OFF
R
CLOSED
R
CLOSED
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
CLOSED
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R
OFF
R