REACTION FORCES
Travel (m)
Area "A"
Indoor lifts & Outdoor
lifts F (kN)
10
14,2
11
14,9
12
15,6
Allowed snow load is 2 kN/m². Verify which snow-load zone the lift is installed in. (EN1991-1-3).

4.2 FORCE ON FIXING TO SUPPORT FRAME (MAST) TO WALL

• c-c = distance (height) from the floor to the highest fixing into the wall. See Fig. 14 Force on fixing to
support frame (mast) to wall
• The maximum distance between two fixings or lower floor and the lowest fixing is 4.0 m.
• The minimum distance between lower floor and the highest fixing is 2.0 m.
• c-t = distance from the top of the mast to highest fixing into the wall. See Fig. 14 Force on fixing to
support frame (mast) to wall
• The maximum distance between the top of the mast and highest fixing is 1.2 m.
16
Area "A"
Area"B"
Outdoor lifts
Isolamin
Snow F (kN)
Shaft F (kN)
4,8
10,20
4,8
11,05
4,8
11,90
7000 100 en-GB AD
Area"B"
Glas
Shaft F (kN)
13,20
14,30
15,40