SiAF341904E
1.2
List of Field Settings for Indoor Unit
Mode
First
Description
No.
Code
(2)
No.
Filter cleaning
sign interval
0
Filter type
1
Remote controller thermistor
10 (20)
2
3
Filter cleaning sign
Remote controller thermistor
6
control during group control
7 (6)
Time for absence area detection
Dry operation time during Eco
10 (7)
mode
Low airflow setting when
11
thermostat OFF during Eco mode
Setting the rate of human
6 (6)
detection
Airflow adjustment
11 (21)
7
Compensating the temperature
8 (6)
around people
Optional accessories output
0
selection (field selection of output
for adaptor for wiring)
External ON/OFF input (Set when
1
ON/OFF is to be controlled from
outside.)
Thermostat differential
2
changeover (Set when remote
12 (22)
sensor is to be used.)
Auto restart after power failure
5
reset
Airflow setting when cooling
6
thermostat is OFF
11 (6) Compensating the floor
temperature
Ceiling height setting, Setting of
0
normal airflow
Airflow direction setting (Set when
1
a sealing material kit has been
installed)
Swing pattern settings
2 (6)
13 (23)
4
Airflow direction adjustment range
6
External static pressure settings
Setting of swing patterns when
7
cooling thermostat is OFF
13
Setting of circulation airflow
14
Circulation airflow patterns
15
Switching panel type
Part 5 Field Settings and Test Operation
Second Code No.
01
Long life filter
Approx.
10,000
Ultra long life
Approx.
filter
Light
Standard filter
Approx.
Long life filter
Remote
controller
thermistor +
Suction air
thermistor
Displayed
Not permitted
30 minutes
30 minutes
Disabled
High sensitivity
OFF
Suction air
temperature only
Indoor unit
turned ON by
thermostat
Forced OFF
1°C
Not equipped
LL tap
4°C
F (4 directions)
All direction
synchronized
swing
Disabled
Pattern 1
Standard panel
02
Approx.
5,000
hrs.
hrs.
Approx.
2,500
Heavy
1,250
hrs.
hrs.
Approx.
200
100
hrs.
hrs.
Ultra long life
filter
Only suction air
thermistor
Not displayed
Permitted
60 minutes
60 minutes
Enabled
Low sensitivity
Completion of
airflow
adjustment
Priority given on
the suction air
temperature
—
ON/OFF control
0.5°C
Equipped
Set fan speed
2°C
Refer to page 120.
T (3 directions)
—
Refer to page 122.
Refer to page 122.
Refer to page 123.
Enabled
Pattern 2
Designer panel
Field Settings for Indoor Unit
: Factory setting
03
04
—
—
—
—
Only remote
controller
—
thermistor
—
—
—
—
—
—
Continuous (not
90 minutes
returning to
cooling)
—
—
Infrared
Standard
presence sensor
sensitivity
disabled
Start of airflow
—
adjustment
Priority given on
Standard
the floor
temperature
Operation output
Error output
External
protection device
—
input
—
—
—
—
—
—
0°C
–2°C
W (2 directions)
—
Facing swing
—
—
—
Pattern 3
Pattern 4
—
—
111