Normal Operation
5.5
Compressor Step Control
The actual rotation speed per second of the compressor (rps) depends on the type of
The change of compressor capacity step corresponds to 1 rps / step.
The control can skip an number of steps to reach faster the target saturation temperature.
5.6
Step Control of Outdoor Fans
Used to control the revolutions of outdoor fans in the steps listed in table below, according to
condition changes.
STEP
No.
RXQ6A
0
0
1
350
2
360
3
370
4
400
5
430
6
490
7Y
520
7X
550
8
565
Note(s)
Figures listed above are for standard mode. Values may differ when the system is set to high
static pressure mode or capacity priority mode.
86
compressor:
Actual rotation
Compressor
speed
(rps)
JT1GUVDYR
frequency/2
JT16KCVDYR
frequency/3
RXQ8/10A
RXQ12A
0
0
350
350
370
370
400
400
460
460
560
560
710
710
750
775
796
870
835
890
RXQ6/8A
RXQ10-14A
M1C
–
M1C
Fan revolutions (rpm)
RXQ14-18A
M1F
M2F
0
0
380
0
470
0
570
0
380
380
550
520
865
665
940
910
1,055
1,025
1,097
1,067
SiAF341904E
Model name
RXQ16/18A
–
M1C, M2C
–
RXQ20A
M1F
0
380
470
570
380
550
865
940
1,136
1,360
Part 4 Functions and Control
RXQ20A
M1C
M2C
M2F
0
0
0
0
380
520
665
910
1,106
1,180