SiAF341904E
When the unit is equipped with an infrared presence/floor sensor:
The thermistor to be used
Remote controller thermistor
Suction air thermistor
Infrared floor sensor
Refer to Compensating the temperature around people.
Note that the control is automatically switched to the one performed only by the suction air
thermistor for indoor unit when the Second code No. is 01 during the group control.
To use the remote controller thermistor during the group control, select the Second code No. 02
in First code No. 6.
10 (20)
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
10 (20)
"Filter Cleaning" is not displayed when an Auto-clean Panel is connected.
Part 5 Field Settings and Test Operation
Mode No.
First Code No.
10 (20)
2
11 (21)
8
Mode
First
Second
No.
Code No.
Code No.
01
6
02
Mode
First
Second
No.
Code No.
Code No.
01
3
02
01
02
01
01
z
z
z
Priority given to
The infrared floor
the suction air
sensor is not used
temperature ( )
Only the suction air
thermistor is used
Remote controller thermistor control is not permitted during
group control
Remote controller thermistor control is permitted during group
control
Field Settings for Indoor Unit
: Factory setting
Second Code No.
02
02#
02
02
03#
04
z
z
z
z
z
z
Priority given to the
floor temperature ( )
Only the remote
Standard setting
controller thermistor
(Factory setting)
is used
Contents
: Factory setting
Contents
Displayed
Not displayed
03
01
z
115