6.2

BRC4C, BRC7E Series

1. Press INSPECTION/TEST button for 4 seconds during normal mode to enter field setting
2. Press INSPECTION/TEST button for 4 seconds to enter service mode.
3. Press MODE buttons to select a desired mode number. (43, 44, 45)
4. Carry out the necessary setting for each mode with UP button or DOWN button.
5. Press RESERVE button to confirm the setting.
6. Press INSPECTION/TEST button to return to normal mode.
Mode
No.
43
44
45
Part 3 Remote Controller
mode.
Function
Content and Operation Method
Forced Fan
Turns the fan ON for each unit
ON
individually.
Individual
Sets fan speed and airflow
Setting
direction for each unit individually
when using group control.
Settings are made using the airflow
direction adjustment and fan speed
adjustment buttons.
Unit No.
Changes unit No.
Change
Set the unit No. after changing with
the programming time up-down
button.
Service Settings Menu, Maintenance Menu
Mode number
UP button
DOWN button
RESERVE button
MODE button
INSPECTION/TEST button
Example of Remote Controller Display