Setting for wireless remote controller (BRC4C, BRC7E series)
The address for the wireless remote controller is set to 1 at the factory. To change the setting,
proceed as follows:
1. Press FILTER SIGN RESET button and INSPECTION/TEST button at the same time for 4
2. Press FAN button and select A or b. Each time the button is pressed, the display switches
3. Press UP button or DOWN button to select an address from 1-3 as same as the receiver.
4. Press RESERVE button to confirm the setting.
5. Press INSPECTION/TEST button for 1 second to return to normal mode.
Field setting mode
Multiple setting
Part 3 Remote Controller
seconds to enter field setting mode. (SETTING is indicated on the display.)
between A and b.
Address can be set from 1-6, but the receiver does not work with addresses 4-6.
Address
Address Setting for Wireless Remote Controller
UP button
DOWN button
FAN button
RESERVE button