Daikin RXQ12AHR Service Manual page 26

Table of Contents

Advertisement

Specifications
Model Name (Combination Unit)
Model Name (Independent Unit)
Power supply
1 Cooling capacity
Casing color
Dimensions (H × W × D)
Heat exchanger
Compressor
Type
Motor output ×
Number of units
Starting method
Fan
Type
Motor output
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Gas pipe
Mass
2 Sound pressure level
Safety devices
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Refrigerator oil
Standard accessories
Drawing No.
Specifications
Sound level
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
20
RXQ20AHRY1
RXQ10ARY1+RXQ10ARY1
3 phase, 380-415 V, 50/60 Hz
kcal/h
Btu/h
191,000
kW
Ivory white (5Y7.5/1)
mm
(1,657×930×765)+(1,657×930×765)
Cross fin coil
Hermetically sealed scroll type
kW
(4.5×1)+(4.5×1)
Soft start
Propeller fan
kW
(0.55×1)+(0.55×1)
m³/min
178+178
Direct drive
15.9 C1220T (Brazing connection)
mm
28.6 C1220T (Brazing connection)
mm
kg
175+175
dB(A)
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector,
Over/under voltage protection printed circuit board
%
kg
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual,
Connection pipes, Clamps
48,200
56
60
13-100
R-410A
6.7+6.7
RXQ22AHRY1
RXQ6ARY1+RXQ8ARY1+RXQ8ARY1
3 phase, 380-415 V, 50/60 Hz
52,300
207,000
60.8
Ivory white (5Y7.5/1)
(1,657×930×765)+(1,657×930×765)
+(1,657×930×765)
Cross fin coil
Hermetically sealed scroll type
(2.3×1)+(3.4×1)+(3.4×1)
Soft start
Propeller fan
(0.55×1)+(0.55×1)+(0.55×1)
119+178+178
Direct drive
15.9 C1220T (Brazing connection)
28.6 C1220T (Brazing connection)
165+165+165
61
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector,
Over/under voltage protection printed circuit board
20-100
R-410A
5.9+5.9+5.9
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual,
Connection pipes, Clamps
Conversion formulae
kcal/h = kW × 860
Btu/h = kW × 3412
Part 1 General Information
SiAF341904E