Standby Control; Restart Standby - Daikin RXQ12AHR Service Manual

Table of Contents

Advertisement

SiAF341904E

3. Standby Control

3.1

Restart Standby

Used to forcedly stop the compressor for a period of 5 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to accelerate pressure
equalizing and to suppress melting of the refrigerant to the evaporator.
Part 4 Functions and Control
Standby Control
81