Daikin RXQ12AHR Service Manual page 123

Table of Contents

Advertisement

SiAF341904E
1.4.7 Setting the Rate of Human Detection
(For units with the infrared presence/floor sensor only)
Set the sensitivity of the infrared presence/floor sensor.
 The infrared presence/floor sensor can be disabled by selecting the Second code No. 04.
When the infrared presence/floor sensor is disabled, the remote controller menu does not
display some functions such as the automatic draft reduction, energy-saving operation in
absence and halt in absence.
11 (21)
1.4.8 Automatic Airflow Adjustment
 FXMQ-PB
The volume of blow-off air is automatically adjusted to the rated quantity.
Make settings before performing the test operation of the outdoor unit.
Setting procedure
1. Make sure that electric wiring and duct construction have been completed. In particular, if
2. If there are multiple blow-off and suction ports, adjust the throttle part so that the airflow
3. Make settings to adjust the airflow rate automatically.
4. After setting, return to the basic screen (to the normal mode in the case of a wireless remote
5. After operation stopped, make sure that the Second Code No. is set to 02 as in the following
11 (21)
Note(s)
1. Make sure that the external static pressure is within the range of specifications before making
settings. If it is outside the range, automatic adjustment fails, which may cause an insufficient
airflow volume or leakage of water.
2. If the air passageway including duct or blow-off ports is changed after automatic adjustment,
make sure to perform automatic airflow adjustment again.
Part 5 Field Settings and Test Operation
Mode
First
Second
No.
Code No.
Code No.
01
02
6
03
04
the closing damper is installed on the way of the duct, make sure that it is open. In addition,
make sure that a field-supplied air filter is installed within the air passageway on the suction
port side.
volume ratio of each suction/blow-off port conforms to the designed airflow volume ratio. In
that case, operate the unit with the operation mode "fan". When you want to change the
airflow rate, adjust it by pressing the airflow rate control button to select High, Middle or Low.
After setting the operation mode to "fan", enter the field setting mode while operation is
stopped and then select the Mode No. "(21) (11 for batch setting)", set the First Code No. to
7 and the Second Code No. to 03.
controller) and press the ON/OFF button. Fan operation for automatic airflow adjustment will
start with the operation lamp turned ON. Do not adjust the throttle part of the suction and
blow-off ports during automatic adjustment. After operation for approximately one to fifteen
minutes, airflow adjustment automatically stops with the operation lamp turned OFF.
table by indoor unit with the Mode No. 11 (21). If operation does not stop automatically or the
Second Code No. is not set to 02, return to the step (3) above to make settings again.
Mode
First
Second
No.
Code No.
Code No.
01
7
02
03
Field Settings for Indoor Unit
Contents
High sensitivity
Low sensitivity
Standard sensitivity
Infrared presence/floor sensor disabled
Contents
OFF
Completion of airflow adjustment
Start of airflow adjustment
: Factory setting
: Factory setting
117

Advertisement

Table of Contents
loading

Table of Contents