SiAF341904E
5.60 System Abnormality, Refrigerant System Address
Undefined
Applicable
All indoor unit models
All outdoor unit models
Models
UH
Error Code
Method of Error
Detect an indoor unit with no auto address setting.
Detection
Error Decision
The error decision is made as soon as the abnormality aforementioned is detected.
Conditions
Supposed
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
Causes
Defective indoor unit PCB
Defective outdoor unit main PCB
Part 6 Service Diagnosis
outdoor units
Troubleshooting by Error Code
285