Circulation Airflow (Fxfsq Only) - Daikin RXQ12AHR Service Manual

Table of Contents

Advertisement

SiAF341904E

8.11 Circulation Airflow (FXFSQ only)

Unevenness of room temperature and the startup time are improved by repeating 2-direction
horizontal blow-off and swing alternately.
8.11.1 Initiation Conditions of Circulation Operation
When operation starts (in the startup state)
Circulation airflow operation is performed.
During normal operation
The unit automatically determines operation based on the room temperature condition and time
to switch circulation airflow operation and the normal auto airflow rate and direction (eco full
automatic control).
Circulation airflow
8.11.2 Operational Concept (Standard Panel)
Cooling
Part 4 Functions and Control
Circulation airflow operation continues for up to 90 minutes
Auto airflow rate and direction
Movement pattern
01: Pattern 1
Appearance
02: Pattern 2
Time (sec.)
03: Pattern 3
13 (23)-14
04: Pattern 4
Indicates the horizontal flap is in the position of reducing airflow volume (the flap is inverted).
Time
(a)
120
120
0
120
Outline of Control (Indoor Unit)
Circulation airflow
Set temp.
Target temp. Δt
(b)
(c)
600
120
600
0
0
120
600
120
: Factory setting
(d)
600
0
600
600
103

Advertisement

Table of Contents
loading

Table of Contents