Advertisement

EDTFVN391825
201803
Engineering Data
FXDQ-SPV1
50 Hz

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FXDQ-SPV1

  • Page 1 EDTFVN391825 201803 Engineering Data FXDQ-SPV1 50 Hz...
  • Page 3: Table Of Contents

    FXDQ-SPV1 EDTFVN391825 FXDQ-SPV1 Slim Ceiling Mounted Duct Type (Compact Series) 50 Hz 1. Lineup ......................2 2. Specifications .....................3 3. Dimensions ....................6 4. Piping Diagrams ..................9 5. Wiring Diagrams ..................10 6. Electric Characteristics ................11 7. Safety Devices Setting ................12 8. Capacity Tables ..................13 8.1 Cooling Capacity for Te: Auto ............13 8.2 Cooling Capacity for Te: 6°C ............13 8.3 Cooling Capacity for Te: 9°C ............14...
  • Page 4: Lineup

    FXDQ-SPV1 EDTFVN391825 1. Lineup 2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW Capacity range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP Capacity index 31.25 62.5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 : 1 phase, 220-240 V, 50 Hz...
  • Page 5: Specifications

    FXDQ-SPV1 EDTFVN391825 2. Specifications Model FXDQ20SPV1 FXDQ25SPV1 Power supply 1 phase, 220-240 V, 50 Hz 1 phase, 220-240 V, 50 Hz kcal/h 1,900 2,400 Btu/h 7,500 9,600 1 3 Cooling capacity kcal/h 2,200 2,800 Btu/h 8,500 10,900 2 3 Heating capacity Cooling 0.072 0.075 Power input Heating 0.056 0.059 Casing / Colour Galvanized steel plate Galvanized steel plate Dimensions: (H×W×D) 200×700×450 200×700×450 Type...
  • Page 6 FXDQ-SPV1 EDTFVN391825 Model FXDQ32SPV1 FXDQ40SPV1 Power supply 1 phase, 220-240 V, 50 Hz 1 phase, 220-240 V, 50 Hz kcal/h 3,100 3,900 Btu/h 12,300 15,400 1 3 Cooling capacity kcal/h 3,400 4,300 Btu/h 13,600 17,100 2 3 Heating capacity Cooling 0.078 0.180 Power input Heating 0.062 0.152 Casing / Colour Galvanized steel plate Galvanized steel plate Dimensions: (H×W×D) 200×700×450 200×900×450 Type Sirocco fan Sirocco fan Motor output ×...
  • Page 7 FXDQ-SPV1 EDTFVN391825 Model FXDQ50SPV1 FXDQ63SPV1 Power supply 1 phase, 220-240 V, 50 Hz 1 phase, 220-240 V, 50 Hz kcal/h 4,800 6,100 Btu/h 19,100 24,200 1 3 Cooling capacity kcal/h 5,400 6,900 Btu/h 21,500 27,300 2 3 Heating capacity Cooling 0.180 0.196 Power input Heating 0.152 0.168 Casing / Colour Galvanized steel plate Galvanized steel plate Dimensions: (H×W×D) 200×900×450 200×1,100×450 Type Sirocco fan Sirocco fan Motor output ×...
  • Page 8: Dimensions

    FXDQ-SPV1 EDTFVN391825 3. Dimensions FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1...
  • Page 9 FXDQ-SPV1 EDTFVN391825 FXDQ40SPV1 / FXDQ50SPV1...
  • Page 10 FXDQ-SPV1 EDTFVN391825 FXDQ63SPV1...
  • Page 11: Piping Diagrams

    FXDQ-SPV1 EDTFVN391825 4. Piping Diagrams FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 / FXDQ63SPV1 4D090514 „ Refrigerant pipe connection port diameters Unit: mm Model Liquid FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 φ12.7 φ6.4 FXDQ63SPV1 φ15.9 φ9.5...
  • Page 12: Wiring Diagrams

    FXDQ-SPV1 EDTFVN391825 5. Wiring Diagrams FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 / FXDQ63SPV1...
  • Page 13: Electric Characteristics

    FXDQ-SPV1 EDTFVN391825 6. Electric Characteristics FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 / FXDQ63SPV1 4D090515...
  • Page 14: Safety Devices Setting

    FXDQ-SPV1 EDTFVN391825 7. Safety Devices Setting Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A Fan motor thermal fuse °C – – – Fan motor thermal OFF: 130±5 OFF: 130±5 OFF: 130±5 °C protector ON : 83±15 ON : 83±15 ON : 83±15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A Fan motor thermal fuse °C...
  • Page 15: Capacity Tables

    FXDQ-SPV1 EDTFVN391825 8. Capacity Tables Cooling Capacity for Te: Auto Indoor air temp. 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB Capacity Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 TC: Total capacity: kW SHC: Sensible heat capacity: kW Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system...
  • Page 16: Cooling Capacity For Te: 9°C

    FXDQ-SPV1 EDTFVN391825 Cooling Capacity for Te: 9°C For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units Indoor air temp. 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB Capacity Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 TC: Total capacity: kW SHC: Sensible heat capacity: kW Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system satisfies the required heat load.
  • Page 17: Fan Performances

    FXDQ-SPV1 EDTFVN391825 9. Fan Performances FXDQ20SPV1...
  • Page 18 FXDQ-SPV1 EDTFVN391825 FXDQ25SPV1...
  • Page 19 FXDQ-SPV1 EDTFVN391825 FXDQ32SPV1...
  • Page 20 FXDQ-SPV1 EDTFVN391825 FXDQ40SPV1 / FXDQ50SPV1...
  • Page 21 FXDQ-SPV1 EDTFVN391825 FXDQ63SPV1...
  • Page 22: Sound Levels

    FXDQ-SPV1 EDTFVN391825 10. Sound Levels FXDQ20SPV1 FXDQ25SPV1...
  • Page 23 FXDQ-SPV1 EDTFVN391825 FXDQ32SPV1 FXDQ40SPV1 / FXDQ50SPV1...
  • Page 24 FXDQ-SPV1 EDTFVN391825 FXDQ63SPV1...
  • Page 25: Centre Of Gravity

    FXDQ-SPV1 EDTFVN391825 11. Centre of Gravity FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 Unit: mm 4D072718G FXDQ40SPV1 / FXDQ50SPV1 Unit: mm 4D072719G...
  • Page 26 FXDQ-SPV1 EDTFVN391825 FXDQ63SPV1 Unit: mm 4D072720H...
  • Page 27: Accessories

    FXDQ-SPV1 EDTFVN391825 12. Accessories 12.1 Optional Accessories (for Controls) Model Item FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Cooling Only BRC4C66 Wireless Remote controller Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller BRC1E62 (Wired remote controller) Remote sensor KRCS01-1B (for indoor temperature) C: 4D090513B...
  • Page 28: I Nstallation Manual

    FXDQ-SPV1 EDTFVN391825 13. Installation Manual Inverter Air Conditioner Installation Manual · CONTENTS Always use separate circuits to supply the power. Any electrical work shall comply with the local laws and 1. SAFETY PRECAUTIONS………………..……. regulations, and at the same time follow the installation instruction manual to ask a qualified professional 2.
  • Page 29: Before Installation

    FXDQ-SPV1 EDTFVN391825 (b) Places in which corrosive gas can be generated, such 2-2 Accessories as sulfur dioxide. Please check whether the following articles are supplied The copper pipes or welded parts can be corroded with the air conditioner. and lead to refrigerant leakage.
  • Page 30: Selecting Installation Site

    FXDQ-SPV1 EDTFVN391825 · b. Key points during inspection when handing over The size of *H in the above figure stands for the minimum height of the air conditioner. Inspected · Items of inspection When selecting *H, the downward slope of at least...
  • Page 31: Indoor Unit Installation

    FXDQ-SPV1 EDTFVN391825 (Unit: mm) Model Inlet air FXDQ20 ~ 32SPV1 FXDQ40 ~ 50SPV1 FXDQ63SPV1 1100 1140 Box cover (2) Please confirm whether the static pressure outside Outlet air the air conditioner exceeds the allowable range. (For the setting range of the static pressure outside the air conditioner, please refer to the technical documents.)
  • Page 32: Refrigerant Piping Work

    FXDQ-SPV1 EDTFVN391825 (1) Connect the pipe. CAUTION · · Refrigerant has been filled in the outdoor unit. Please use a water level or water filled polyethylene · Align the connecting section of the refrigerant pipe to pipe to confirm whether the air conditioner is installed the center of the flare section, and firstly turn 3 –...
  • Page 33: Drain Piping Work

    FXDQ-SPV1 EDTFVN391825 Table 2 CAUTION Recommended length Pipe dimension Angle to be further tightened 1. In case that nitrogen is filled into the pipe when welding, of the tool arm a relief valve shall be used to control the pressure to Ø...
  • Page 34 FXDQ-SPV1 EDTFVN391825 · · The water drainage pipe shall be short as possible and Please keep the water drainage riser pipe vertical, tilt downward, and the slope shall be at least 1/100, and ensure that the distance from the air conditioner is within 300 mm.
  • Page 35: Installing The Duct

    FXDQ-SPV1 EDTFVN391825 (2) When the pipe work is completed, please check 8. INSTALLING THE DUCT whether the water drainage is smooth. Please connect the air pipe supplied on site. Air inlet side Case for Model FXDQ ~ SPV1 · Please install the flange on the air supply side (supplied on site).
  • Page 36 FXDQ-SPV1 EDTFVN391825 · Never connect the grounding cable to any gas pipe, 7. As the unit is equipped with a frequency converter, running water pipe, lighting rod or telephone line. to prevent misoperation of the electricity leakage · Gas pipe : Once any gas is leaked out, exposition and circuit breaker itself, please use a product which can fire can happen.
  • Page 37: Wiring Example

    FXDQ-SPV1 EDTFVN391825 10. WIRING EXAMPLE [Notes] · For the installation and wiring of the remote control, 10-1 Connection of the power cables please refer to the “Installation manual for the remote · As shown in the Fig. 14, please open the electrical box control”...
  • Page 38 FXDQ-SPV1 EDTFVN391825 [Wiring Examples] System 3 Case with BS device installed Power supply CAUTION single phase Outdoor unit BS device 1~ 220-240 V In case that the connected outdoor unit is 24 kW 50 Hz or below, please comply with the following items.
  • Page 39 FXDQ-SPV1 EDTFVN391825 10-2 Double controls for one unit (One indoor unit [Notes] · controlled by two remote controls) In case that control by group and double remote · controls are used at the same time, it is required to When two remote controls are used, one must be set connect a jump cable.
  • Page 40: Field Setting And Test Run

    FXDQ-SPV1 EDTFVN391825 11. FIELD SETTING AND TEST RUN 11-3 Setting the time to display the clean air filter element signal · (The field setting of the following items shall be To change the “Setting for contamination level of the completed with the operation of the remote control air filter element”, tell the following contents to the user.
  • Page 44 VRV is a trade mark of Daikin Industries, Ltd. VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982. VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”...

Table of Contents