Daikin RXQ12AHR Service Manual page 124

Table of Contents

Advertisement

Field Settings for Indoor Unit
1.4.9 Compensating the Temperature around People
(For units with the infrared floor sensor)
Change the ratio between the suction air temperature and floor temperature used to calculate
the temperature around people.
The temperature around people is calculated using the values of the suction air thermistor and
the infrared floor sensor. The factory setting is "Normal" (the average value of the suction air
temperature and the floor temperature is applied). However, the rate at which the suction air
thermistor and the infrared floor sensor affect the temperature around people can be changed
with this setting.
 To reflect the effect of the temperature around the ceiling, select the "Priorities given on the
 To reflect the effect of the temperature around the floor, select the "Priorities given on the
 The infrared floor sensor can be disabled by selecting "Suction air temperature only" (the
11 (21)
1.4.10 Optional Accessories Output Selection
Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals X1 and X2 of "adaptor for wiring", an optional
accessory.
12 (22)
1.4.11 External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T2 terminal of the operation terminal block in the electrical
component box.
12 (22)
118
suction air temperature" (the Second code No. 02).
floor temperature" (the Second code No. 04).
Second code No. 01).
Mode
First
Second
No.
Code No.
Code No.
01
02
8
03
04
Mode
First
Second
No.
Code No.
Code No.
01
02
0
03
04
Mode
First
Second
No.
Code No.
Code No.
01
02
1
03
Suction air temperature only
Priority given on the suction air temperature
Standard
Priority given on the floor temperature
Indoor unit thermostat ON/OFF signal is provided.
Output linked with ON/OFF of remote controller is provided.
In case of Error Display appears on the remote controller, output is
F2 T1 T2
Forced OFF
Input A
ON: Forced OFF (prohibition of using the remote controller)
OFF: Permission of using the remote controller
OFF  ON: Operation
ON  OFF: Stop
ON: Operation
OFF: The system stops, then the applicable unit indicates A0. The
other indoor units indicate U9.
Part 5 Field Settings and Test Operation
SiAF341904E
: Factory setting
Contents
: Factory setting
Contents
provided.