8.5

Auto Draft Reducing Control (FXFSQ only)

In the case where both this control is activated and auto airflow direction control (eco full
automatic control) is set, when human presence is detected, the airflow direction is
automatically set to horizontal (P0) to reduce discomfort by direct airflow.
This control works for each airflow outlet individually.
Note: This function is inoperative for the airflow outlet where an individual airflow direction is set.
8.6

Eco Full Automatic Control (FXFSQ only)

This is a generic term for the setting where both fan speed and airflow direction are set to
"Auto." For detailed control contents, refer to Automatic Airflow Rate Control and Airflow
Direction Control.
Part 4 Functions and Control
Absence continues for 5 mins
P0 (horizontal)
When presence is detected
Outline of Control (Indoor Unit)
Airflow direction by auto airflow direction
Cooling: P0 or P1
97