Centralized Control Group No. Setting
5.2

BRC4C, BRC7E Series

Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, press INSPECTION/TEST button for 4 seconds or more to enter
field setting mode.
2. Set mode No. 00 with MODE button.
3. Set the group No. for each group with UP button or DOWN button.
4. Enter the selected group numbers by pressing RESERVE button.
5. Press INSPECTION/TEST button and return to the normal mode.
Field setting mode
RESERVE button
5.3

Group No. Setting Example

Indoor/Outdoor Outdoor/Outdoor
F1 F2
Caution
When turning the power supply on, the unit may often not accept any operation while 88 is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.