Model Name
Power supply
1 Cooling capacity
Casing color
Dimensions (H × W × D)
Heat exchanger
Compressor
Type
Motor output ×
Number of units
Starting method
Fan
Type
Motor output
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Gas pipe
Mass
2 Sound pressure level
Safety devices
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Refrigerator oil
Standard accessories
Drawing No.
Specifications
Sound level
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Part 1 General Information
RXQ6ARY1
3 phase, 380-415 V, 50/60 Hz
kcal/h
Btu/h
kW
Ivory white (5Y7.5/1)
mm
1,657×930×765
Cross fin coil
Hermetically sealed scroll type
kW
Soft start
Propeller fan
kW
m³/min
Direct drive
9.5 C1220T (Brazing connection)
mm
19.1 C1220T (Brazing connection)
mm
kg
dB(A)
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector,
Over/under voltage protection printed circuit board
%
kg
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual,
Connection pipes, Clamps
3D120745
4D112438A
13,800
54,600
16.0
2.3×1
0.55×1
119
165
56
25-100
R-410A
5.9
RXQ8ARY1
3 phase, 380-415 V, 50/60 Hz
19,300
76,400
22.4
Ivory white (5Y7.5/1)
1,657×930×765
Cross fin coil
Hermetically sealed scroll type
3.4×1
Soft start
Propeller fan
0.55×1
178
Direct drive
9.5 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
165
56
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector,
Over/under voltage protection printed circuit board
20-100
R-410A
5.9
Electronic expansion valve
Refer to the nameplate of compressor
Installation manual, Operation manual,
Connection pipes, Clamps
3D120745
4D112439A
Conversion formulae
kcal/h = kW × 860
Btu/h = kW × 3412
Specifications
27