Index Features ..............................4 Unit Description and configurations......................5 Standard material name – base module ....................6 Specifications ............................. 7 4.1. Technical Data ............................7 4.1.1. Nominal Data ........................... 7 4.1.2. Sectioning ............................8 4.1.3. Nominal Air Flow ........................... 11 4.2.
Page 3
5.3. Accessories only for Pro version ......................27 5.3.1. Useful information ......................... 27 5.3.2. Coils ............................... 28 5.3.3. Valves ............................. 31 5.3.4. Dampers ............................32 5.3.5. Electrical accessories ........................32 5.4. Accessories only for Smart version ....................... 33 5.4.1. Coils ............................... 33 Performance ............................
Ideal solution for light commercial applications as: retail shops, small and large offices, hotels, gyms, cinemas, theatres, school, colleges, universities, etc • Left or right hand version • Smart (Daikin F1-F2/P1-P2 communication protocol) or Pro (Open protocol) version Databook Modular T - October 2022 - Rev. 00...
2. Unit Description and configurations Modular T is available in two configurations for connection side, right and left (looking to the position of supply air flow standing in front of the installed unit). Right version Components: 1. Bypass damper 2. Ducts 3.
For Smart version, the BRC thermostat/remocon is not included with the main unit and has to be povided separately. Nomenclature: Main Unit Main Unit Modular T Modular T Smart Right Left Right Left Size 03 ATB03RA ATB03LA Size 03 ATB03RAS ATB03LAS Size 04 ATB04RA ATB04LA Size 04 ATB04RAS ATB04LAS Size 05 SB.ATB05RA SB.ATB05LA...
4.1.2. Sectioning To ensure an easy and quick transportation and installation biggest sizes are provide in more sections. The following table summarize the number of sections for each size. Material Name Size Number of sections ATB03*A* ATB04*A* ATB05*A* ATB06*A* ATB07*A* For the units provided in more sections, size 05, 06 and 07, there is an easy rule to follow up, to identify the position of the sections, valid for both right and left version of the unit.
Page 9
Size 05 – Right configuration Size 05 – Left configuration Supply air Return air Fresh air Exhaust air Databook Modular T - October 2022 - Rev. 00...
Page 10
Size 06 & 07 – Right configuration Size 06 & 07 – Left configuration Supply air Return air Fresh air Exhaust air Databook Modular T - October 2022 - Rev. 00...
4.1.3. Nominal Air Flow 3900 Size 7 2700 Size 6 2300 Size 5 1650 Size 4 Size 3 1000 1500 2000 2500 3000 3500 4000 4500 Air Flow rate (m From 200 up to 4200 m Nominal airflow m For any performances out of the nominal condition here above mentioned kindly refer to the online selection software available online at tools.daikinapplied.eu 4.2.
4.3. Declaration EU. REG. 1253/2014 Material Name ATB03*A* ATB04*A* SB.ATB05*A* SB.ATB06*A* SB.ATB07*A* Size Manufacturer’s name Daikin Applied Europe Typology (NRVU, UVU / BVU) * NRVU BVU Type of drive Inverter (included on the electronic fan) Type of HRS Other Thermal efficiency of 76.8...
4.4. Bearing structure The units feature double-skin panels that consist of two folded steel sheets. Panel thickness is 50 mm for all unit sides. The standard versions provide Aluzinc AZ185 for the inner skin and pre-coated steel for the outer skin.
4.8. Filters Filter types are plane (compact) made with fibreglass material. All the filters - regardless of their type – are mounted in opportune rails equipped with a mechanical frame that maintains the filters in pressure a high sealing along the full perimiter. The available filter grades are: G4), M5),...
The units, in fact, can accommodate on supply air stream up to three filters at the same time (M5+F7+F9). In order to avoid the fast clogging of the fine filter from gross particles, units can also provide a class G4 pre –...
Daikin on Site 4.9.2. Smart Controls Modular T Smart can be directly integrated into DIII-net ecosystem and controlled through any Daikin local, centralised controllers (iTAB, iTM, iTC) or Cloud controllers (Daikin Cloud Service). This communication, based on the common F1-F2 and P1-P2 protocol, guarantees also fully compatibility with SkyAir and VRV systems.
Modular T Control Control platform Daikin Control PCB Remote controller Room controller: Optional BRC 1 [E/H] Co2 control Optional, BRYMA2000 sensor BACnet or Modbus integration Through interfaces (optional) Cloud connection Daikin Cloud Service 4.10. Default Values 4.10.1. Pro Version All the unit are pre factory set at nominal value summarize in the table below. All the values can be changed using the Commissioning Module (ALC00895A).
4.10.2 Smart version Factory set values for nominal operating airflow and corresponding setting for the BRC1[E/H]. Please refer to the IOM, in order to determine new operating points and new unit setting for various speeds. Size 03 Supply Exhaust Volume Flow rate Volume Flow rate 2310 2276...
4.11.2. Smart Version In accordance with the image here below showed, adding a pre-electrical heater (ATD**HEFBU) is mandatory for outdoor temperature lower than -5°C for either tackling or preventing frost issue. Main Module ATB*S SB.ATB*S Main Module ATB*S / SB.ATB*S Preheating electric coil ATD*HEFBU …...
Page 21
Databook Modular T - October 2022 - Rev. 00...
Please refer to the Installation and Operation Manual (IOM) for further information. 4.12. Operating Limits Modular T heat recovery units are designed for use in indoor environments, installed on the floor. The unit cannot operate in environments containing explosive material and with a high concentration of dust. Thanks to its modularity, each machine is able to adapt to different needs in terms of air flow and thermodynamic treatments.
4.12.2. Smart Version Lower limit Upper limit Configuration Size temperature (°C) temperature (°C) without coil -5°C 46°C Outside air temperature with pre heating coil -25°C 46°C Operating environment 5°C 46°C temperature Temperature of environment with the -40°C 60°C machine off (e.g., storage, transport, etc.) Databook Modular T - October 2022 - Rev.
5.2. Accessories for Pro & Smart version 5.2.1. Filters The unit is provided as standard with ePM1 50% (F7) filter on supply side and ePM1 75% (M5) filter on return. On supply side up to three filtration stages as available. It is not possible to install the third filtration stage and the water post heating coil at the same time.
5.2.2. Silencers Silencers for supply and or return ducts are available for each size. The length of silencer is 600mm. They are circular, in this way no duct transitions are needed. In the next table, there are attenuation data for each frequency: Frequency [Hz] Material...
The unit gets delivered with its nominal air flow rate set up at factory. To adjust its operation to the project-specific parameters, kindly select the optional commissioning module ALC00895A or refer to Daikin Service Dept. Alternatively, you can also commission the units using the web server HMI access (default feature) •...
Page 29
A cooling and heating DX coil is available as accessory to guarantee the thermal treatment. In the Astra Web report, the Daikin Electronic Valve Kit (EKEXV*) model which has to be site installed, is specified. The DX coil must be installed inside the unit along with its drip collection tray. Please follow the dedicated IOM for further information on the installation procedure.
Page 30
5.3.2.3. Electrical pre and post heating coil For each size, two electrical heaters are available for selection, with the following material name and features: Material Max Power Electric Diameter / Length Height Weight Size Name Output (Kw) Data Depth (mm) (mm) (mm) (kg)
5.3.2.5. Water post-heating coil A heating water coil is available as accessory as post heating. The coil is mounted outside the main module. Please follow the dedicated IOM for further information on the installation procedure. Following table summarizes main technical data for post heating water coil. ATD03HWSAL ATD04HWSAL ATD05HWSAL...
5.3.4. Dampers Two type of dampers are available as option for Modular T: mixing damper to allow recirculation and external dampers for AHU isolation. 5.3.4.1. Mixing Damper A mixing Damper is available as accessory to allow recirculation of the air, saving energy and consequently decrease running cost of the unit.
5.3.5.4. Digital PCB for external accessories For accessories mounted externally to the main unit, which require to be controlled, it is mandatory to add a further digital PCB (ATE00DPUA). The following components require Electric pre and post heating coils Water preheating coil Digital PCB is also needed when additional filters are mounted and it is required to monitor pressure drop for each filtration stage, according to VDI6022.
6. Performance This section summarizes the main technical data for each size: envelope for each unit, thermal efficiency of the heat exchanger and sound emission at different operating points. More details about measurements done are collected in the next paragraphs. 6.1.
Page 35
Size 04 1000 SFPv 1200 SFPv 1600 SFPv 2000 1250 1750 2250 Air Flow [m Size 05 SFPv 1200 SFPv 1600 SFPv 2000 1000 2000 3000 Air Flow [m Databook Modular T - October 2022 - Rev. 00...
6.2. Thermal efficiency The charts indicate the thermal efficiency of the heat exchanger at the follwing conditions: Wet efficiency: -5°C/ RH 90% Outdoor and +22°C/50% Indoor With air ratio 1:1 and according to EN308 Thermal efficiency: Size 03 Thermal efficiency: Size 04 Databook Modular T - October 2022 - Rev.
6.3. Sound emission Surrounding power level: The airborne is the sound power emitted by the unit. The surrounding power level is the logarithmic sum of the two airborne values (supply and return). Surrounding pressure level: It is calculated in accordance with EN3744. The evaluation is done at 1 meter from the source and with a directivity factor equal to 4, in non-reverberant field.
Page 40
Sound Level Size 04 Air flow: 1200 m /h, ESP: 50 Pa Point Frequency (Hz) 1000 2000 4000 8000 (dBA) Supply inlet Supply outlet Sound power Return inlet (dB) Return outlet Surrounding power Surrounding pressure (dBA) Air flow: 1500 m /h, ESP: 50 Pa Point Frequency (Hz)
Page 41
Sound Level Size 05 Air flow: 2100 m /h, ESP: 50 Pa Point Frequency (Hz) 1000 2000 4000 8000 (dBA) Supply inlet Supply outlet Sound power Return inlet (dB) Return outlet Surrounding power Surrounding pressure (dBA) Air flow: 2500 m /h, ESP: 50 Pa Point Frequency (Hz)
Page 42
Sound Level Size 06 Air flow: 2600 m /h, ESP: 50 Pa Point Frequency (Hz) 1000 2000 4000 8000 (dBA) Supply inlet Supply outlet Sound power Return inlet (dB) Return outlet Surrounding power Surrounding pressure (dBA) Air flow: 2750 m /h, ESP: 50 Pa Point Frequency (Hz)
Page 43
Sound Level Size 07 Air flow: 3000 m /h, ESP: 50 Pa Point Frequency (Hz) 1000 2000 4000 8000 (dBA) Supply inlet Supply outlet Sound power Return inlet (dB) Return outlet Surrounding power Surrounding pressure (dBA) Air flow: 4000 m /h, ESP: 50 Pa Point Frequency (Hz)
6.4. Dimensional Drawings Dimension Drawing: Size 03 Databook Modular T - October 2022 - Rev. 00...
Page 45
Dimension Drawing: Size 04 Databook Modular T - October 2022 - Rev. 00...
Page 46
Dimension Drawing: Size 05 Databook Modular T - October 2022 - Rev. 00...
Page 47
Dimension Drawing: Size 06 Databook Modular T - October 2022 - Rev. 00...
Page 48
Dimension Drawing: Size 07 Databook Modular T - October 2022 - Rev. 00...
Page 49
All the technical data and performances included within this document are subject to change without prior notice. Please refer to the last version of selection software available online for updated information (tools.daikinapplied.eu) Databook Modular T - October 2022 - Rev. 00...