Monitor Mode (Mode 1) - Daikin RXQ12AHR Service Manual

Table of Contents

Advertisement

SiAF341904E
2.5

Monitor Mode (Mode 1)

In the monitor mode, information can be retrieved about settings related to performance,
addresses, number of units and actual operation data.
2.5.1 Retrieve data by using BS button outdoor unit main PCB
To enter monitor mode, press the
MODE (BS1) button while in
normal mode.
Selecting monitoring item
Press the SET (BS2) button to set
the 7 segment display to any of the
monitoring items listed in the table below.
Checking for description of data
Press the RETURN (BS3) button.
Data on the monitoring item selected will
appear on the 7 segment display.
Press the RETURN (BS3) button to
set monitor mode to the initial state.
Press the MODE (BS1) button will return
the mode to normal mode.
∗ If you lose setting in progress,
press the MODE (BS1) button.
You should return to normal mode.
Legend Segment
Part 5 Field Settings and Test Operation
: OFF
: ON
Field Settings for Outdoor Unit
SEG1 SEG2 SEG3
Normal
BS1
MODE
BS2
SET
BS3
RETURN
BS3
RETURN
BS1
MODE
Normal
: BLINKS
: hold 5 seconds
135

Advertisement

Table of Contents
loading