SiAF341904E
Operation
sound
Time set with night-time low
noise operation start setting
Rated
Level 1
Level 2
Level 3
Low noise mode
instructing Operation sound
set with external low noise
setting
Set with night-time low noise operation start
setting. (Factory setting is 10:00 PM.)
 m2-30: Power consumption limitation level 1. If the system needs to be running under
 m2-31: Power consumption limitation level 2. If the system needs to be running under
 m2-38: Emergency operation "Master". To disable permanent compressor operation: in
Part 5 Field Settings and Test Operation
 When operation parameters return to normal range, the capacity priority is switched OFF,
enable to reduce airflow rate depending on night-time low noise operation is still required
(end time for low night noise operation is not reached or external input night-time low
noise operation is still closed).
If capacity priority is set in
capacity priority setting, the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
∗Operation sound mode
set with night-time low
noise operation setting
8:00 PM
10:00 PM
12:00 AM
power consumption limitation conditions via the external control adaptor for outdoor unit
DTA104A61/62. This setting defines the level power consumption limitation that will be
applied for level 1. The level is according the table.
 Default: 3 (70%)
 Field setting:
set 2-30
current limit set (%)
1
60
2
65
3
70 (default)
4
75
5
80
6
85
7
90
8
95
power consumption limitation conditions via the external control adaptor for outdoor unit
DTA104A61/62. This setting defines the level power consumption limitation that will be
applied for level 2. The level is according the table.
 Default: 1 (40%)
 Field setting:
set 2-31
current limit set (%)
1
40 (default)
2
50
3
55
case of single module or "Master" unit of a multi outdoor system, this setting allows:
 Default value: 0. Compressor operation enabled.
 Field setting:
 Set 1: inverter 1 compressor is disabled.
 Set 2: inverter 2 compressor is disabled. Only to make in case of 16-20 HP. Note that
compressor 2 is left side located.
 Set 3: all compressors in this master module are disabled permanent.
Time set with night-time low
noise operation end setting
∗Night-time
∗Low noise
mode instructing
∗Operation sound set with
external low noise setting
6:00 AM 7:00 AM 8:00 AM
Set with night-time low noise operation end
setting. (Factory setting is 8:00 AM.)
Field Settings for Outdoor Unit
147