Field Settings for Outdoor Unit
Step 1:
Mode 2-28
Set 01 02, then
press "Return" twice
Check 1
Check 2
Magnectic
K1M OFF
Check 1 : AC power input (connector X10A on A2P: inverter compressor) 380-415 V
unbalance max. 2%.
Check 2 : relay "K1M" on inverter PCB switches: check DC voltage on P&N increase to
±500 VDC.
Check 3 : DC = 1.42 x VAC power supply L1-L3: check at connector X3A (8-12 HP), or
X5A, X6A (14-20 HP).
Check 4 : AC U/V/W 10 Hz intermediate: check difference within 10 V (at fasten U/V/W)
Check 5 : AC U/V/W 240 Hz continuous output while voltage drop (discharge capacitors
DC) check difference between U/V/W within 10 V. 2 LEDs (V phase) brightness
reduce until OFF.
*Note: Actual voltage value depends on meter characteristics
m2-29: Capacity priority. When the night-time low noise operation is in use, performance of
146
In case there is more than 1 compressor in a system (outdoor is 14 HP or larger, or
multi outdoor configuration) all compressor inverter PCBs will perform the power
transistor check. In such case, disconnect U/V/W fasten terminals on all
compressors. Avoid accidental touch of fasten terminals to short-circuit or earth leak
to casing.
To stop the power transistor check mode, change setting to default 2-28-0.
Output to U/V/W will also stop when outdoor unit main PCB decides standby mode of
inverter circuit.
Next time graph shows the different steps during the power transistor check mode.
Switching sequence during power transistor check mode:
Disconnect U/V/W from compressor before
performing the power transistor check.
Voltage
output
Magnectic
U/V/W
switch (K1M)
ON
±100V
AC*
Check 3
±6 sec
Voltage
output
U/V/W
switch
±170
VAC*
±3 sec
system might drop because airflow rate of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: capacity priority can temporary cancel the night-time low noise operation.
Capacity priority can be initiated when certain operation parameters approach the safety
setting:
Raise in high pressure during cooling.
Raise of discharge pipe temperature.
Raise of inverter current.
Raise of fin temperature inverter PCB.
Check 4
Frequency: 10 Hz
±3 sec
Check 5
Frequency: 240 Hz
±30 sec
Part 5 Field Settings and Test Operation
SiAF341904E
Step 2:
Mode 2-28
Set 02 01, then
press "Return" twice
OR press "MODE" button
±60 VAC*