Wiring the GRAFIK Eye

QS Link Control Wiring Details

• System communication uses IEC PELV wiring.
• Follow all local and national electrical codes when
installing IEC PELV wiring with line voltage/mains
wiring.
• Each terminal accepts up to two 1.0 mm
• Total length of control link must not exceed
610 m.
• Make all connections in the control unit's wallbox.
• Wiring can be T-tapped or daisy-chained.
• IEC PELV 24 V
150 mA.
System Limits
The QS wired communication link is limited to 100
devices or 100 zones.
The GRAFIK Eye
QS control unit supplies 3 Power
®
Draw Units (PDUs) on the QS link. Refer to the
QS Link Power Draw Units specification submittal
(Lutron PN 369405) for more information concerning
Power Draw Units.
Wire Sizes (check compatibility in your area)
QS Link Wiring Length
Less than 153 m
153 to 610 m
®
QS Control Unit:
®
wires.
2
Wire Gauge
Power (terminals 1 and 2)
1 pair 1.0 mm
2
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
Power (terminals 1 and 2)
1 pair 4.0 mm
2
Data (terminals 3 and 4)
1 twisted, shielded pair 0.5 mm
For additional information, see the complete installation and operation guide at www.lutron.com/qs
LUTRON
LUTRON
GRAFIK Eye
control unit
QS smart
power
panel
Sivoia
QS
®
window
treatment
Daisy-Chain Wiring Example
GRAFIK Eye
QS
®
control unit
LUTRON
Lutron Cable Part Number
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
2
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
2
GRAFIK Eye
QS Control Unit Quick Installation and Operation Guide 7
®
LUTRON
T-Tap Wiring Example
QS
seeTouch
®
wallstation
LUTRON
LUTRON
LUTRON
Sivoia
®
QS
GRAFIK Eye
QS
®
window
control unit
treatment
LUTRON
LUTRON
QS smart
power panel
LUTRON
LUTRON
LUTRON
QS
®
seeTouch
QS
®
wallstations