5-2-2-4. Standard Muting Mode with four Muting Sensors using PNP Outputs

The following is the example of External Device Monitoring disabled, Auto Reset mode, PNP output
and External Test in 24 V Active.
[DIP Switch settings] *5
EDM Disabled (factory default setting)
Receiver
Auto Reset (factory default setting)
PNP (factory default setting)
Emitter
External Test: 24 V Active (factory default setting)
Configure functions with the DIP Switches before wiring.
[Wiring Example]
F39-JG A-L
B1
Reflector
Muting
Sensor
A1
(PNP
output)
*1. Also used as Override input line.
*2. Make sure to connect an override cancel switch to the Reset line when
using the override function. Otherwise the override state may not be
released by the override cancel switch, resulting in serious injury.
*3.Refer to 5-4. Connectable Safety Control Units for more information.
*4.The safety controller and the F3SG-R must share the power supply or
be connected to the common terminal of the power supply.
*5. The functions are configurable with DIP Switch. Refer to Chapter 3
Setting with DIP Switch for more information on setting the functions
by the DIP Switch.
*6. When connecting to the PLC, the output mode must be changed with
the Configuration Tool according to your application.
Function
F39-JG A-D
S2
S1
*2
B2
A2
Input/Output Circuit and Applications
DIP-SW1
: Indicates a switch position.
IN
IN1
IN2
PLC *6
Safety
Controller *3 *4
+24 VDC
Power Supply
0 VDC
S1: Test Switch (Connect the line to 0 V if this
switch is not required)
S2: Lockout/Interlock Reset Switch,
Override Switch or Override Cancel Switch
A1, A2, B1, B2: Muting sensor
Unblocked
Beam state
Blocked
Test Switch (S1)
MUTE A
MUTE B
OSSD
DIP-SW2
F3SG-R
199
User's Manual
E