5-2-2-2. F3SG-RA with Y-Joint Plug/Socket Connector in Standard Muting
Mode/Exit-Only Muting Mode using PNP outputs
The following is the example of External Device Monitoring disabled, Auto Reset mode, PNP output
and External Test in 24 V Active.
[DIP Switch settings] *5
EDM Disabled (factory default setting)
Receiver
Auto Reset (factory default setting)
PNP (factory default setting)
Emitter
External Test: 24 V Active (factory default setting)
Configure functions with the DIP Switches before wiring.
[Wiring Example]
F39-GCNY2
F39-JG B-L
S1
*2
S1: Lockout/Interlock Reset Switch,
Override Switch or Override Cancel Switch
ML: Muting Lamp
*1. Also used as EDM input line.
*2. Make sure to connect an override cancel switch to the
Reset line when using the override function. Otherwise
the override state may not be released by the override
cancel switch, resulting in serious injury.
*3. Refer to 5-4. Connectable Safety Control Units for
more information.
*4. The safety controller and the F3SG-R must share the
power supply or be connected to the common terminal
of the power supply.
*5. The functions are configurable with DIP Switch. Refer
to Chapter 3 Setting with DIP Switch for more
information on setting the functions by the DIP Switch.
*6. When connecting to the PLC, the output mode must be
changed with the Configuration Tool according to your
application.
Function
F39-JG A-D
IN1
IN1
IN2
Safety
PLC *6
Controller *3 *4
Beam state
Input/Output Circuit and Applications
DIP-SW1
DIP-SW2
: Indicates a switch position.
+24V DC
Power supply
0V
Unblocked
Blocked
MUTE A
MUTE B
OSSD
E
F3SG-R
197
User's Manual