System Operation and Functions
2 or fewer are blocked
14-mm dia. max.
Lockout
Fig. 3
 Detection Capability
Detection capability for F3SG-RA differs based on the number of floating beams as shown below.
Model
F3SG-4RA-14
F3SG-4RA-30
 F3SG-R LED Indicator status
When floating blanking is being enabled, the Blanking indicator turns on.
Refer to 2-1. Combination of Functions for more information on the use in conjunction with other functions.
2-15-2. Factory Default Setting
The factory default setting is the Floating Blanking Disabled.
2-15-3. Setting with DIP Switch
Configuring the blanking setting of the DIP switch as Floating Blanking Enabled enables the floating
blanking function.
The floating blanking monitoring function is configured as lockout.
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Refer to Chapter 3 Setting with DIP Switch for more information on setting this function by the DIP Switch.
F3SG-R
84
User's Manual
More than one zone is blocked
Safety output OFF
Number of beams configured
-
1 beam
2 beams
3 beams
4 beams
n beams
-
1 beam
2 beams
3 beams
4 beams
n beams
30-mm dia.
30-mm dia.
Fig. 4
Number of blocked beams to turn safety
Detection capability
14 mm
24 mm
34 mm
44 mm
54 mm
14+(10×n) mm
30 mm
50 mm
70 mm
90 mm
110 mm
30+(20×n) mm
outputs OFF
1 beam
2 beams
3 beams
4 beams
5 beams
(n+1) beams
1 beam
2 beams
3 beams
4 beams
5 beams
(n+1) beams