Omron F3SG-2RE0430P30 User Manual page 95

Safety light curtain
Table of Contents

Advertisement

Refer to 2-24-6. Muting Statistics Information for more information.
Standard Muting Mode
Function
Muting zone
Bottom beam
Top beam
T1
: Muting input time limit value (minimum)
min
T1
: Muting input time limit value (maximum)
max
T2: Muting time limit
T3: Maximum allowable muting signal interruption
Exit-Only Muting Mode
Function
Muting zone
Bottom beam
Top beam
T1
: Muting input time limit value (minimum)
min
T1
: Muting input time limit value (maximum)
max
T2: Muting time limit
T3: Maximum allowable muting signal interruption
T4: Muting end wait time
T5: Exit-only muting delay time
Position Detection Muting Mode
Function
Muting zone
Bottom beam
Top beam
T1
: Muting input time limit value(maximum)
max
T2: Muting time limit
T3: Maximum allowable muting signal interruption
Dynamic Muting
Function
Dynamic muting
Dynamic muting measurement time
Number of dynamic muting allowable beams
Make sure the Position 8 of the DIP Switch is set to Configuration Tool Enabled to activate the settings by the
Configuration Tool.
Setting the muting time limit to infinite may cause a failure of the muting sensors to go undetected, resulting in the F3SG-RA
in an unintended muting state. Conduct risk assessment analysis thoroughly before enabling this setting.
Setting the muting input time limit value (maximum) to infinite may cause a failure of the muting sensors to go
undetected, resulting in a failure of disabling the muting state. Conduct risk assessment analysis thoroughly before
enabling this setting.
Dynamic Muting can be used in conjunction with any of Standard, Exit-only and Position detection muting modes.
Refer to Safety Light Curtain Configuration Tool for Model F3SG (SD Manager 2) User's Manual for more
information on setting this function by the Configuration Tool.
System Operation and Functions
Factory Default Setting
All beams
any beam in 1-beam increments
0.1 s
0.1 to 3.9 s in 0.1-s increments
4 s
0.2 to 60 s in 0.1-s increments, or infinite
60 s
1 to 600 s in 1-s increments, or infinite
0.1 s
0.1 to 20 s in 0.1-s increments
Factory Default Setting
All beams
any beam in 1-beam increments
0.1 s
0.1 to 3.9 s in 0.1-s increments
4 s
0.2 to 4 s in 0.1-s increments, or infinite
60 s
1 to 600 s in 1-s increments, or infinite
0.1 s
0.1 to 4 s in 0.1-s increments
1 s
0.1 to 20 s in 0.1-s increments
4 s
4 to 20 s in 0.1-s increments
Factory Default Setting
All beams
any beam in 1-beam increments
4 s
0.2 to 60 s in 0.1-s increments, or infinite
60 s
1 to 600 s in 1-s increments, or infinite
0.1 s
0.1 to 4 s in 0.1-s increments
Factory Default Setting
Disable
Enable/Disable
3 s
1 to 25 s in 0.1-s increments
1
0 to 5 in 1-beam increments
Available Parameters
Available Parameters
Available Parameters
Available Parameters
F3SG-R
User's Manual
E
71