Operation Check While The Machine Is Stopped - Omron F3SG-2RE0430P30 User Manual

Safety light curtain
Table of Contents

Advertisement

down.
Model of emitter and receiver must be the same.
When 2 or more F3SG-R systems are used, they are in cascade connection or prevented from mutual
interference with each other.
On a secondary sensor farthest from its power supply, either of the following is attached:
- End Cap
- Lamp (F39-LP and F39-BTLP, sold separately)
- Bluetooth
®
Communication Unit (F39-BT, sold separately)
Neither connector, cap, or bracket must be loose.
Auxiliary output must not be used as safety output.
When using PNP output, 0 V line of the power supply is grounded. When using NPN output, +24 VDC
line of the power supply is grounded.
Wiring must not be bent, cracked, nor damaged.

6-1-1-3. Operation Check While the Machine Is Stopped

The test rod is not deformed.
The object resolution may vary depending on the models of the F3SG-R and settings of floating
blanking function or reduced resolution function. Use a test rod with an appropriate diameter for
inspection. A test rod is not included in the F3SG-R product package.
The sensor can detect a test rod wherever it is in the detection zone. In other words, when a test rod
is inserted into the detection zone, the Stable-state indicator turns OFF and the ON/OFF turns red.
When fixed blanking function is used, you must ensure that all blanked zones in the detection zone
are covered by a hard barrier guard and there must be no zone in the detection zone where the test
rod goes undetected.
To check detection, move the test rod as shown in the diagram below.
When the external test function is used:
When 24 V Active is enabled by the DIP Switch, the ON/OFF-state indicator turns red when the TEST
line is short-circuited to 9 V to Vs.
When 0 V Active is enabled by the DIP Switch, the ON/OFF indicator turns red when the TEST line
is short-circuited to 0 to 3 V.
When the external device monitoring function is used:
When the RESET line is open the ON/OFF indicator remains red regardless of the beam state of the
F3SG-R.
When the start interlock function is used:
When the F3SG-R is turned ON and the F3SG-RA is unblocked, the ON/OFF indicator remains red.
The RESET input turns the ON/OFF indicator to green.
When the restart interlock function is used:
Start
Stop
Checklists
E
F3SG-R
215