Wiring Examples(F3Sg-Ra Series); Standalone F3Sg-Ra Using Pnp Outputs; Auto Reset Mode, Edm Disabled And Pnp Outputs - Omron F3SG-2RE0430P30 User Manual

Safety light curtain
Table of Contents

Advertisement

Input/Output Circuit and Applications

5-2. Wiring Examples(F3SG-RA Series)

Examples of a motor control system using the F3SG-RA are shown below. This chapter shows examples
equivalent to up to PLe, Category 4 (ISO13849-1).

5-2-1. Standalone F3SG-RA using PNP Outputs

5-2-1-1. Auto Reset Mode, EDM disabled and PNP Outputs

The following is the example of Muting disabled, External Device Monitoring disabled, Auto-Reset
Mode, PNP outputs and External Test in 24 V Active.
[DIP Switch settings] *1
Receiver
Emitter
Configure functions with the DIP Switches before wiring.
[Wiring Example]
Beam state
The wiring examples in later pages do not indicate functional earth. To use functional earth, wire an earth cable
according to the example above. Refer to 4-5-5. Functional Earth Connection for more information.
F3SG-R
192
User's Manual
Function
EDM Disabled (factory default setting)
Auto Reset (factory default setting)
PNP (factory default setting)
External Test: 24 V Active (factory default setting)
F39-JG A-L
Unblocked
Blocked
OSSD
DIP-SW1
F39-JG A-D
KM1
KM2
KM1, KM2: Safety relay with forcibly guided contacts (G7SA)
or magnetic contactor
M: 3-phase motor
*1. The functions are configurable with DIP Switch. Refer to
Chapter 3 Setting with DIP Switch for more information on
setting the functions by the DIP Switch.
DIP-SW2
: Indicates a switch position.
KM1
KM2
+24 VDC
Power Supply
0 VDC
Functional Earth
M