7.13.2 External control variable (External measurement probe)
You only need to read further here if you have connected an external temperature probe or the actual temperature is
read in from a module (and you have activated it as control variable according to ( Section 7.7.4)).
Only modify the control parameters if you have knowledge of control techniques.
The control system for external actual values is implemented for improvement of the control behavior as a two-stage
cascade controller. A "master controller" determines the "internal setpoint", from the temperature setpoint and the ex-
ternal temperature, passed to the slave controller. The control value of the slave controller controls the heating.
When a setpoint step change is specified, it may be that the optimum control would set a bath temperature, which
might significantly exceed the temperature desired on the external vessel. There is a correction limitation, which speci-
fies the maximum permissible deviation between the temperature on the external load and the bath temperature.
Master
3x
to
MNEnu
1x
to
P1d..
EP !5
E
Et0l
76 / 123
P1d..
As shown in the menu structure ( 7.6), the parameters for the external
control variable can now be set.
Select the parameter with
displayed. Adapt it with
Example: Proportional factor of the master controller Kpe = 1.5.
Parameters Master controller (PIDT
Ma proportional factor:
°C
Ma proportional range:
Ma reset time:
Ma derivative time (auto/ man)
The thermostat logic system only permits values with Tne > Tve!
Ma damping time (auto/ man)
Parameter Slave controller (P-controller):
Sl proportional range:
Tve, Tde, Prop_E changeover to Auto/ Man E
Manual.
°C
A
Works setting is Automatic. These three parameters should only be modified
by experienced control technicians!
Hold
Correction limitation Et0l . See introduction ( 7.13.2).
°C
Proline heating thermostat
or
or
confirm with
-controller):
1
pressed for 3s, then make changes.
and confirm with
. The set value is
.
= Kpe
as factor.
EP
= Prop_E in Kelvin.
Eb
= Tne
in seconds.
En
= Tve
in seconds.
Ev
= Tde
in seconds.
Ed
= Xpf
in Kelvin.
iP
A = Automatic or MN =
02/2022