Page 1
Operating instructions PROLINE heating thermostat Thermostats with PowerAdapt system Heating thermostats P 5 C Calibration thermostat PJ 12 C, PJL 12 C Clear view thermostats PV 15 C, PVL 15 C, PV 24 C, PVL 24 C, PV36 C Bridge thermostats PB C, PBD C Read the instructions before starting all work!
Page 2
Manufacturer LAUDA DR. R. WOBSER GMBH & CO. KG Laudaplatz 1 97922 Lauda-Königshofen Germany Phone: +49 (0)9343 503-0 Fax: +49 (0)9343 503-222 E-Mail info@lauda.de Internet https://www.lauda.de Q4DA-E_13-009-DE-01 Translation of the original operating instructions English / Release 02/2022 A Valid from: Software of Operating system (Command) version 3.45...
Prefixed safety notes Before operating the equipment please read carefully all the instructions and safety notes in Section 1. If you have any questions please phone us! Follow the instructions on setting up, operation etc. This is the only way to avoid incorrect operation of the equipment and to ensure full warranty protection.
Safety information General safety information A laboratory thermostat heats and circulates liquids according to specified parameters. This involves hazards due to high temperatures, fire and general hazards due to the application of electrical energy. The user is largely protected by the application of relevant standards. Further hazard sources may arise due to the type of tempering medium, e.g.
Other safety information Only connect equipment to PE grounded mains sockets. At higher operating temperatures, parts of the bath cover can reach surface temperatures exceeding 70 °C. Be careful when touching it Risk of burning! Use suitable hoses ( 6.4). Secure hose against slippage with the aid of hose clips.
Brief operating instructions These brief instructions shall give you the possibility to operate the unit quickly. For safe operation of the unit, it is absolutely necessary to read carefully all the instructions and safety notes! 1. Assemble unit and add items as appropriate ( 6.1). Take care of the hose tubing connections (...
Page 10
Menu structure: Command remote control intern Pt100 Pump Level Calibration Menu extern Pt100 Default Calibration all default All Modules Works settings Master Resolution All default Command Device status Only control par. int. Contact Display data Only control par. ext. Other connected Basic settings Only miscellaneous modules...
Controls and functional elements Command remote control (see page 16) Bath cover Master control panel (see page 16) Recessed grip Mains switch 4 Feet Pump connection at side and bypass-valve (see illustration below) Side pump connection: Pumpe outflow, pressure output (closed off with screw plug) Bypass valve (in “external”...
Page 12
Cover for the two module slots Mains supply head Rear pump connection: Connection socket for the external Pt100 temperature probe Suction nozzle (return to bath) Connection socket (CAN 1 and 2) for bus suitable for unit and to Pumpe outflow (pressure output) which the refrigerating lower section and Command remote control 10 Cooling coil: Cooling water inlet connection are connected.
Page 14
Control element: “Master” Display : Cooler active (blue LED is lit) : The temperature of an external source is displayed : Bath controlled by external temperature (EXT is lit green). source (green LED lits) : Error signal (red LED blinking) : Enter key : Select keys : Overtemperature set point to check or set Tmax...
P 5 C is a Bath thermostat with 5-liter bath and Command remote control. PVL 15 is a clear view thermostat with 15-liter bath and operating temperature up to -60 °C (with LAUDA add-on cooler). PJ 12 C is a calibration thermostat with 12-liter bath and Command remote control.
At the right-hand side and at the back of the unit outflow and inflow nozzles are fitted for external loads. This means that up to two external loads can be directly connected without a distributor. Connections which are not required must be closed off with the supplied caps and union nuts.
The Master unit is equipped with the following sockets at the back of the control head: For the connection of an external Pt100 temperature sensor (10S). Two sockets (70S) for the connection of components via the LAUDA equipment bus (cooling section, Command remote control, external solenoid valve, etc.).
4. Contact Module (Order No. LRZ 914) with connector to NAMUR NE28. Functionality as LRZ 915, but only one output and one input on each of two DIN sockets. Coupling socket 3-pole, LAUDA Order No. EQD 047 and coupling plug 3-pole, LAUDA Order No. EQS 048.
After unpacking, firstly check the device and accessories for any damage in transit. If, contrary to expectations, there is visible damage to the unit, the carrier must be immediately informed, so that an investigation can be made. Please also inform the LAUDA Service (Contact 9.4). Standard Accessories:...
Preparation Assembly and sitting Site the unit on a flat surface The unit must not be put into operation if its tem- perature during storage or transport has dropped below the dew point. Wait for about one hour. ...
When operating Proline heating thermostats above 100 °C to 300 °C, we recommend the LAUDA high-temperature cooler HTC, order number LCZ 9663. Operation with high-temperature cooler 02/2022...
Page 22
For bath temperatures above 155 °C it is not allowed to cool with water together with the simple cooling coil (water vapor risk of explosion). Especially for the Proline there is a controlled high temperature cooler for fast and time saving cooling with bath temperatures up to 300 °C (accessory LCZ 9663).
Filling and draining Filling Close the drain cock! Carefully remove all residues of the previous heat transfer liquid (blow dry and remove screw plugs!). Maximum filling level is up to 10 mm below the top edge of the bath. Overfilling leads to the dis- WX103 play of the warning (...
Observe the safety data sheets for the various heat transfer liquids. If required, you can download the safety data sheets from our homepage. Open the LAUDA homepage, tap Services Download center. In the Download center, chose the [Safety data sheet] option in the [Document type] drop-down list.
Page 25
Temperature range °C Field of application (cm) MC 50 LZM 040 — MC 100 LZM 041 — With simple insulation, for all LAUDA heat transfer liquids MC 150 LZM 042 — MC 200 LZM 043 — MK 50 LZM 052 —...
Connecting external loads Operation as circulating thermostat Bursting of the external consumer due to overpressure Scalding, frostbite, cutting Use a pressure relief device on pressure-sensitive consumers (e.g. glass reactors). When used as circulation thermostat, care for shortest hose connections with largest inner diameter as possible. This gives the best flow.
Starting up Mains connection Compare the rating on the nameplate (back of control head) with the mains voltage. Connect unit only to sockets with a protective earth conductor (PE). No liability is accepted for incorrect mains connections! Ensure that pump connectors without external loads are closed off. ...
Page 28
LEUEL Display for (low level) appears when the bath has too little liq- Level alarm uid. °C LEUEL Red LED above the fault triangle flashes. Find cause of fault and, where necessary, top up missing heat transfer liquid (...
Switching off / standby Switching off: Set mains switch to position 0. Standby operation: Use the key on the Command remote control. The pump and heater are switched off. The operating display remains active, so that the device status is visible and adjustments can be made. The timer continues to run.
Page 30
The following always applies: After termination of the relevant settings, they are accepted automatically after approx. 4 s or the setting is accepted immediately with the Enter key. Fault signal: Flashing red Alarm LED and acoustic signal. ...
Page 31
Brightness Contrast Brightness Display The brightness and contrast can be set on the Sounds Master Contrast Command remote control: Sounds Command Language The works setting can be changed via Master-Mode Settings Basic settings Autostart Display Brightness or ...
Page 32
2. Standard window with five important items of °C Level information: T , current bath temperature, °C T , setpoint, T , current temperature on external probe (if connected), °C Pump Level of heat transfer liquid in cm above the minimum level, ...
7.4.2 Changing window information Command Display data You can adapt the information displayed by your °C Level Command remote control to your requirements. For example, if you have not connected any tem- perature probe, you can exchange it in the standard °C setting of the normal window for the maximum tem- perature T...
7.4.3 Locking the keyboard The keyboards of the Master and the Command remote control can be locked independently of one another. This is especially advantageous when the thermostat is positioned in another room and the Command remote control is used as a remote control device.
Page 35
Command Locking: Press and then and hold pressed simul- Locking keyboard! taneously for 3 s. The locking window appears. Hold both keys pressed until the progress bar is completely filled. Then the display skips back to the previously set Screen mode.
UEr Software version Cur Max. current consumpt. Section 9.2.2 Menu structure: "Master" Section 7.7.5 S Setpoint resolution Snr_H Serial number Hi Word. MNEmv 2 dots in the display, e.g. , indicate that a Section 7.8.1 Section 9.2.3 submenu follows. StArt Opern. w. mains fail. Snr_L Serial number Lo Word.
Menu structure: Command remote control intern Pt100 Pump Level Calibration Menu extern Pt100 Default Calibration all default All Modules Works settings Master Resolution All default Command Device status Only control par. int. Contact Display data Only control par. ext. Other connected Basic settings Only miscellaneous modules...
Important settings 7.7.1 Temperature setpoint setting The setpoint is the temperature which the thermostat should reach and maintain constant. Master (main level) Press key until (Setpoint) appears. Press, display flashes. Enter the setpoint with the two keys ( Section 7.4.1 General key func- tions and pilot lamps).
Page 39
Confirm the value with or quit the window with without having made any changes. Two other ways of entering the setpoint: Fixed settings Recent setpoints With the soft key open the window 0,00°C 80,00°C shown on the left. 0,00°C -35,50°C ...
7.7.2 Displaying the actual external temperature With all Proline Thermostats an external temperature probe can be connected, which for example..1..can be used as an independent temperature measurement channel. 2..can be used as the controlled variable for the bath temperature in applications with a noticeable tem- perature gradient (between the internal bath temperature and an external load).
Command Provided an external temperature probe is con- °C Level nected, its value is displayed in the lower left part of the standard and super windows (applies to the works setting for the window partitioning). °C External actual temperatures can also be read in via interface modules.
Command Pump level Open the device parameter menu via the soft Level 8 Pump level Menu . Level 7 Level 6 Change from Pump Pump level using Level 5 With you enter the illustrated win- Level 4 dow.
Change temperature probe source: for the internal probe, only when an external probe is connected, only when an analog module is connected and configured, only when a serial module is connected and is continuously receiving ac- tual values from a PC.
Page 44
Master Call current consumption MNEnu PArA The present setting is displayed. °C 1&0 The current consumption is shown flashing: e.g. Set the required maximum current consumption (in A). wait 4 seconds or Display flashes 4 s new value is automatically accepted, or ...
7.7.6 Setting the date and time Command Clock Time Date Open the device parameter menu via the soft Pump Set time Settings Set date Menu . Graph Timer 1 With the cursor keys continue to: Clock Timer 2 Clock Set time Programmer...
Select the desired resolution with Accept selection with or End , Display resolution 0,01 or quit the window with without making 0,001 changes. Pump Menu Special settings 7.8.1 Setpoint resolution This function enables the resolution of the setpoint T to be increased from the standard value of 0.1 °C to 0.01 °C (only Master).
Page 47
StArt Master StArt Call the start option MNEnu PArA The start mode can be changed here. °C StArt Auto MNAn The display flashes. Auto , when operation is be restored automatically again after an inter- ruption. MNAn , when the standby mode is to be activated after a mains interrup- ...
7.8.3 Defining temperature limits With this function it is possible to define a minimum and a maximum temperature in which the thermostat controls. By reaching the temperature limits, a warning appears. In this way setpoint input can be prevented which may damage the heat transfer liquid or the apparatus.
Enter the desired limit temperature. Accept the change with Lower limit (Til) or quit the window with without making -50, changes. Min: -50,0 °C Max: 301,0 °C Help Menu Screen 7.8.4 Setpoint offset operating mode With this function it is possible to apply an offset value to the temperature provided by the external temperature probe or a module and then to use it as the setpoint.
Page 50
Command Offset source Setpoint offset Open the device parameter menu via the soft Offset source Setpoint offset extern Pt100 Menu . RS232 With the cursor keys continue to: Control Setpoint offset Offset source indicates that the setpoint offset is cur- ...
7.8.5 Restoring works settings Master If you would like to restore all the works settings except the control parameters and the probe calibrations call the works settings MNEnu PArA is displayed. °C Press longer than 3 seconds. 3 seconds long donE ...
Page 52
Under Master you have the choice between: All default , then all Master settings are reset, only control para int for the internal con- trol parameters, only control para ext similar for external, only miscellaneous which resets set- ...
7.8.6 Setting the volume of the acoustic signals The LAUDA Proline Thermostats signal alarms as a dual-tone acoustic signal and warnings as a continuous tone. Audio Master Audio Call the volume setting ( 7.5). MNEnu PArA Audio takes you to the alarm volume, °C...
7.8.7 Entering the offset of the internal temperature probe If, during checking with a calibrated reference thermometer probe, a deviation is found, then the offset (i.e. the additive part of the characteristic) of the internal measuring chain can be adjusted with the following function. The reference thermometer must be dipped into the bath according to the details on the calibration certificate.
The temperature measurement device shows the true temperature value (with glass ther- Temperature value of the ref. mometers consider the correction where appli- temp. measurement device: cable!). Change the display in the adjacent window to the true value with cursor or soft keys and ac- cept with or End , Min: -50,0°C...
Confirm the control dialog on the right with or cancel with Confirm input! Return to the measurement window with Enter key: Continue End or Escape key: Cancel Pump Menu 7.8.9 Entering the offset of the external temperature probe If a deviation is found during the check using a calibrated reference thermometer probe, then the offset (the additive part of the characteristic) of the external measurement chain can be adjusted with the following function.
7.8.10 Restoring the works setting of the external temperature-probe offset If the offset has been misadjusted unintentionally, the works setting can be restored with this function. dEF E Master Call the offset works setting for the external temperature probe MNEnu CAL..
Graphical display of temperature measurements Command Screen and Graph 25,00 25,01 25,02 Press the soft key Screen a number of T °C 27,00 times as required until the graph recorder win- dow appears. 26,00 25,00 With the soft key Graph you enter the menu for the configuration of the graph record- 24,00...
Page 59
Temp. scale defines how the scaling is to be carried Mode Temp. min 22,00 out: Displayed value Temp. max 27,00 Automatic , by the program, or Legend Sample time Manual in that you yourself define the limits Time axis with the next menu point.
7.10 Programmer (PGM) Almost any temperature/time profile can be created with the programmer. A desired bath temperature can be approached as quickly as possible or via a defined ramp. Furthermore, the pump level and the behavior of the switching outputs can be defined.
Page 61
Each program begins with the segment "Start". It defines at which temperature Segment 1 is to contin- ue the program. It is not possible to specify a time for the Start segment. Without the Start segment, Segment 1 would be different depending on the bath temperature at the start of the program. For heating thermostats the start temperature must be set above the actual bath temperature during program start together with a sufficient tolerance to allow reaching the set temperature without cooling (especially if no additional cooling is available).
°C Example for the influence of the Tolerance field input in case of external bath temperature control: The setpoint temperature of the programmer is shown in grey. The actual temperature in the external bath contain- er is represented as a continuous line. ...
Commands, which depending on the situation cannot be executed, are not displayed. Continue therefore only appears, when Hold has been activated. Once the start has been confirmed with Hold Status Prog. 1 running appears at the bottom. Stop Edit Loops Graph Info...
Continue Status In addition, the standby key stops the pro- Stop Edit grammer! Pump and heater are switched off. Loops Follow the safety information ( 7.7.3). Graph Info After pressing the standby key again, the programmer returns to the previously selected operating mode: Pause or active operation depending on what was previously selected.
Page 65
Command Programmer Program1 Edit Modify In the Edit menu one can Modify Delete Status Modify a program. Delete Edit Press the key. Loops Graph Continue to Modify . with the key Info There is the possibility of modifying single seg- ments, i.e.
Page 66
If the tolerance range has been selected too small, it may be that the program does not continue, be- cause the required tolerance is never achieved. External temperature control: Especially with ramps, a too close tolerance range can cause undesired delays in the start phase of the ramp.
Page 67
If the field in the column Time has a black background, the entry mode for the "Segment time" time setting is obtained by pressing the key. Input segment time: If 0 is entered into the field "Time", ------ ap- pears.
Page 68
The contact outputs of the contact module (if ------- Contact out present, special accessory) are programmed Open here. Closed If the field in the column "Out 1" has a black background, the entry mode for the Contact output is obtained by pressing the key.
7.10.5 Defining the number of program loops (Loops) Command Programmer Program1 Loops If required, programs can be looped many Status times. Edit With access the menu Loops Loops Graph Select the number of desired program loops. Info Pump Menu ...
The display of the programmed temperature T °C 27,00 curve can be quit with or End . 26,00 25,00 24,00 23,00 Pump 00:00 Menu 00:45 01:30 02:15 7.10.7 Obtaining information on a program (Info) Command Programmer Program1 Info Continue with to Info.
7.11 Ramp function With the ramp function temperature changes over any time period can be conveniently entered. This is especially ad- vantageous with very low temperature changes (e.g. 0.1 °C per day). Example: From the current outflow temperature (e.g. 242.4 °C), 200 °C of cooling is to occur over 5 days. Then the temperature change is entered as 200 °C and the time as 5 days.
7.12 Timer function Using the timer function, the thermostat can carry out an action at a certain time or after a certain waiting period. The actions are: Switching on the thermostat, entering the standby mode or one of the five programs in the programmer. Command Timer 1 Timer 2 ...
Page 73
Week plan Week plan Arrange takes you to the win- Time Action Time Action dow shown on the left. Monday 07:30 Start 17:00 ------- Using the cursor keys select the field, Tuesday 10:00 Prog.4 17:00 ------- which is to be filled in. Wednesday 08:00 ------- 17:00 ------- ...
7.13 Control parameters The control parameters are optimized ex-works for operation as a bath thermostat (with water as the heat transfer liq- uid) with internal control. The parameters are also preset for the operation of external containers with external control. Sometimes however, the operation of external containers requires adaptation.
Command Control Parameters Open the device parameter menu via the soft Control Parameters Control para. sets Menu . (auto) Tv manual/auto With the cursor keys continue to: (auto) Control Control Parameters Control Parameters The adjacent window appears. ...
7.13.2 External control variable (External measurement probe) You only need to read further here if you have connected an external temperature probe or the actual temperature is read in from a module (and you have activated it as control variable according to ( Section 7.7.4)). Only modify the control parameters if you have knowledge of control techniques.
Command Control Parameters Open the device parameter menu via the soft Control Parameters 0,50 Control parameter sets Menu . Tve (auto) 83 Tv manual/auto With the cursor keys continue to: Tde (auto) Correction limitation Control Control Parameters Con- ...
Page 78
Ethanol Minimum 40 °C Tools to watch the time behavior: Graph mode of the Command remote control, LAUDA Wintherm PC-program. 78 / 123 Proline heating thermostat 02/2022...
7.13.3 Internal and external control parameter sets If a thermostat is used for a number of applications, which always leads to a change of the control parameters, these control parameters (up to 9 sets) can be saved in the thermostat and activated again as required. Also saving is useful for finding the best control parameters;...
Errors: When an error occurs, switch of the device. If the error is always present after switching on the de- vice, please inform the LAUDA Service ( 9.4). Find cause of alarm or warning and rectify where necessary. Then press on the Master keyboard in order to remove the alarm message.
Page 81
Quit the change mode by pressing again or automatically after 5 seconds, while you keep pressed. This somewhat complicated procedure is intended to prevent unintentional adjustment. Set the overtemperature switch-off point Tmax below the flash point of the heat transfer liquid (...
If irregularities arise during the checking of the safety devices, switch off the unit immediately and pull out the mains plug! Have the equipment checked by LAUDA Service. Command Low-level alarm! Low-level alarm is shown in the display and signifies that unlocking is only possible on the ...
7.14.3 High-level settings Different reactions can be chosen when the level sensor detects the height of the heat transfer liquid level. Depending on the setup, heat transfer liquid or operation conditions, one of the following settings may be suitable: Setting Master set- Command set- Reaction and application recommendation...
7.14.4 High-level warning or alarm Acoustic warning signal sounds for 3 seconds when the liquid level rises so far 3 Sec. that the uppermost switching point of the level sensor has been reached. Or in case the warning function as described in ( 7.14.3) was chosen: ...
7.14.5 Pump-motor supervision: Overload or blockage The SelfCheck Assistant monitors the Varioflex Pump: 1. Alarm sounds as dual-tone signal for pump-motor overload or blockage. bL0C 2. Display of signals blockage. Pump alarm °C 3. Red LED above the fault triangle flashes.
7.14.7 Fault list “Alarms and Warnings” Alarms Message Meaning Pump too fast (low level) PuLEU Low level alarm in the level sensor LEUEL Overtemperature (t > tmax) tEMNP Pump blocked (no rotation) bL0C Command connection interrupt CFA1L Temperature signal of external Pt100 missing Temperature signal of analogue input missing Temperature signal of serial port missing Analogue module: Current input 1 interrupted...
Page 87
Warnings from “Command-Display” Warnings from “Cooling system” Message Meaning Message Meaning Overflow of CAN receipt Overflow of CAN receipt WX201 WX301 Watchdog-Reset Watchdog-Reset WX202 WX302 RTC Voltage drop recognised: Battery failure sm.stell_min still not determined Adaption run WX203 WX303 necessary Software version of control system too old Pressure switch 1 operated...
Page 88
Software version of Pump 0 too old Software version of Pump 0 too old WX421 WX521 Software version of Pump 1 too old Software version of Pump 1 too old WX422 WX522 Software version of Pump 2 too old Software version of Pump 2 too old WX423 WX523 Software version of Pump 3 too old...
Interface modules Installing modules The master and command can be supplemented with further interface modules which are simply inserted at the back of the control head into two module slots. Touch the earthed bath cover of the Proline thermostat to discharge any electrostatic charge.
Menu structure for all modules All existing menu points are illustrated. However, the Command remote control masks out menu points, which cannot be executed. Further information can be found in the following sections. RS232 RS485 2400 Setpoint temperature Menu Ext. actual temp. 4800 9600 Pump power...
RS 232/485 interface module (catalogue no. LRZ 913) with 9-pole SUB-D socket. Electrically isolated by opto- coupler. With the LAUDA instruction set essentially compatible to the ECO, Ecoline, Integral XT and Integral T Se- ries. The RS 232 interface can be connected directly to the PC with a 1:1 through-contact cable (catalogue no. EKS 037).
8.3.2 Protocol RS 232 The interface operates with 1 stop bit, no parity bit and 8 data bits. Transfer rate either: 2400, 4800, 9600 (factory setting) or 19200 baud as selected. The RS 232 interface can be operated with or without hardware handshake, (RTS/CTS). ...
An RS 485 bus always requires bus termination in the form of a termination network which ensures a defined rest status in the high-resistance phases of bus opera- tion. The bus termination is as follows: This termination network is usually incorporated on the PC plug-in card (RS 485). 8.3.4 Protocol RS 485 ...
Page 94
OUT_PAR_07_XX.X Setting of control parameter TdE OUT_PAR_09_XXX.X Setting of the correction limitation OUT_PAR_10_XX.X Setting of control parameter XpF OUT_PAR_14_XXX.X Setting of the setpoint offset OUT_PAR_15_XXX Setting of control parameter PropE OUT_MODE_00_X Keyboard Master: 0 = free / 1 = locked (corresponds to “KEY”) OUT_MODE_01_X Control: 0 = internal / 1 = external Pt100 / 2 = external Analogue / 3 = external Serial...
8.3.6 Read commands (Data requested from the thermostat) Command Explanation IN_PV_00 Read bath temperature (outflow temperature) IN_PV_01 Indication of the controlled temperature (internal/external Pt/external Ana- logue/external Serial) IN_PV_03 Read external temperature TE (Pt100) IN_PV_04 Read external temperature TE (Analogue input) IN_PV_05 Read current bath level IN_PV_10...
® with the aid of the National Instruments program development tool LABVIEW (http://sine.ni.com/apps/we/nioc.vp?cid=1381&lang=US). In order to make program operation possible on the RS 232/485 interface, LAUDA provides drivers specially de- ® signed for LABVIEW which can be downloaded free of charge underFehler! Hyperlink-Referenz ungültig..
Analogue module The analogue module (order no. LRZ 912) has 2 inputs and 2 outputs which are brought out on a 6-pole DIN socket to Namur Recommendation (NE28). The inputs and outputs can be set independently as 4 – 20 mA, 0 –...
Contact module 8.5.1 Contact module LRZ 915 with three inputs and three outputs Contact module Cat. No. LRZ 915) on 15 pole SUB-D socket. With three relay contact outputs (changeover, max. 30 V/0.2 A) and three binary inputs for control via external voltage-free contacts. The following functions are made available by the inputs: Set fault with function: Master: F ALA or Command: Fault...
8.5.2 Namur-Contact module LRZ 914 with only one input and one output Contact module (Cat. no. LRZ 914) with connector to NAMUR NE28. Functionality as LRZ 915, but only one out- put and one input on each of two sockets. Contact module LRZ 914;...
Maintenance Cleaning Withdraw the equipment mains plug before cleaning! Cleaning can be carried out with water to which a few drops of surfactant (washing-up liquid) have been added and using a damp cloth. No water must enter the control section! ...
9.2.4 Device data Master MNEmv ShoWX ( Section 7.5) Various device datas are displayed. Command Device data Settings Device status Device T ext Pt 25.70 Tint 25,58 data Display T ext analog ---.-- Mains U(%) 103.74 T ext serial ---.-- Mains Frequ.
Keep to service intervals ( 9.3.2). If servicing does not occur at the stated intervals, then the manufacturer can no longer guarantee the safe operation of the thermostatic circulator. 9.3.1 Servicing LAUDA Thermostats largely require no service. If the heat transfer liquid becomes contaminated, it should be re- placed ( 6.3). ...
9.3.4 Repair information If you need to send in a unit for repair, it is essential to first contact the LAUDA Service ( 9.4). If the equipment does have to be returned to the factory, it may only be necessary to dismantle the control head from the bath vessel and return the control head.
Service, ordering replacement parts and rating label When ordering spares please state the serial number (rating label). This avoids queries and supply of incorrect items. Rating label Contact the LAUDA Service in the following cases: In the event of faults on the device For technical questions about the device ...
PC Program as a graph with free choice of time frame. Incl. RS 232 cable (2 m). RS 232/485 Interface modules Digital Communication, operation of the LAUDA PC LRZ 913 software Wintherm Plus ( 8.3) Analogue module Current and voltage interface ( 8.3.1)
Page 107
Round cover for PJ 12, PJ 12 C, PJL 12, PJL 12 C. HDR 028 LiBus = LAUDA internal BUS (based on CAN) ID = Immersion depth for test tubes We will inform you about other accessories on request ( 9.4). Also, refer to our special and accessory broachers.
Technical data and diagrams The figures have been determined according to DIN 12876 Heating thermostat P 5 C Working temp. range (WT) °C 35 – 300 WT with water cooling °C 20 – 300 Operating temperature range °C -30 –...
Page 109
Table 2 Clear view thermostats PV 15 C PV 24 C PV 36 C PVL 15 C PVL 24 C Working temp. range (WT) °C 30 – 230 30 – 230 30 – 230 30 – 100 30 – 100 ...
Page 110
Table 3 Bridge thermostats Calibration thermostats PB C PBD C PJ 12 C PJL 12 C Working temp. range (WT) °C 30 – 300 30 – 300 30 – 300 30 – 200 WT with water cooling °C 20 – 300 20 –...
Page 111
Data applicable to all Proline heating thermostats Ambient temperature range °C 5 – 40 Relative humidity maximum relative humidity 80 % for temperatures up to 31 °C, decreasing line- arly to 50 % relative humidity at 40 °C Storage temperature range °C -20 –...
Page 112
Heating curve for P 5 C, PJ 12, PJL 12 (PJL 12 up to 200 °C) measured with Ultra 300, bath covered Heating curve for PV 15, PV 24, PV 36, PVL 15, PVL 24 (PVL 15 and PVL 24 up to 100 °C) measured with Ultra 230, bath covered 112 / 123 Proline heating thermostat...
Page 113
Pump characteristics measured with water 02/2022 Proline heating thermostat 113 / 123...
Page 114
Pump characteristics measured with water 114 / 123 Proline heating thermostat 02/2022...
Need help?
Do you have a question about the PROLINE P 5 C and is the answer not in the manual?
Questions and answers