Process Image
Table 21: Process Image of the I/O Module, Examples of Process Values
Input
Current
4 mA ... 20 mA
< 4.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
> 20.0
1)
Bit B2: not defined
Bit B1 and bit B0: Indicates if the measuring range is overrange / underrange or if there is a wire break
Manual
Version 1.3.0
Numeric Value
Binary
Binary
Measured Value
Diagn.
'00000000.00000 x11'
'00000000.00000 x00'
'00001111.11111 x00'
'00011111.11111 x00'
'00101111.11111 x00'
'00111111.11111 x00'
'01001111.11111 x00'
'01011111.11111 x00'
'01101111.11111 x00'
'01111111.11111 x00'
'01111111.11111 x11'
WAGO-I/O-SYSTEM 750 XTR
750-455/040-000 4AI 4-20mA S.E. /XTR
Hex.
1)
0x0003
0x0000...0x0004
4088...4092
0x0FF8...0x0FFC
8184...8188
0x1FF8...0x1FFC
12280...12284
0x2FF8...0x2FFC
16376...16380
0x3FF8...0x3FFC
20472...20476
0x4FF8...0x4FFC
24568...24572
0x5FF8...0x5FFC
28664...28668
0x6FF8...0x6FFC
32760...32764
0x7FF8...0x7FFC
0x7FFF
Status
LED
Byte
Error
Hex.
AI 1...4
Dec.
3
0x41
On
0...4
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
32767
0x42
On