Byte Mailbox; Table 17: Process Values For The Hart Module, Namur Ne43 Format - WAGO 750-482/000-001 Manual

2ai 4-20ma hart namur ne43, 2-channel analog input, 4 ma … 20 ma hart, namur ne43
Table of Contents

Advertisement

30
Process Image

Table 17: Process Values for the HART Module, NAMUR NE43 Format

Input Current
3.6 mA ... 21 mA
< 1.0
Wire Break
< 3.6
Underrange
3.6
3.8
4.0
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
20.0
20.5
21.0
Overrange
> 21.0
Short Circuit
> 23.0
Status bits: F = Underrange, O = Overrange
1)
4.1

6 Byte Mailbox

In the "6-byte mailbox" operating mode the HART module provides the fieldbus
coupler/controller with a 12-byte input and output process image via one logical
channel.
1 control byte (C0) and 1 status byte (S0) are used to monitor the data flow.
The data is mapped in the cyclic process image of the connected
coupler/controller. However, the HART commands can then be implemented by
the "WagoLibHart_0x.lib" PLC library. The data is tunneled to the application via
a mailbox and decoded by means of the library so that evaluation and processing
take place directly at the application level.
The IEC application can be implemented in the connected programmable
fieldbus controller (PFC) of the fieldbus node with the WAGO-I/O-PRO
programming tool or, if a fieldbus coupler is connected, in the superimposed
controller.
Manual
Version 1.0.2
750-482/000-001 2AI 4-20mA HART NAMUR NE43
Numeric Value
Binary
FO
Measured Value
'1111.1100.1111.11 11'
'1111.1100.1111.1 11'
'1111.1100.1111.1 11'
'1111.1110.0111.1 00'
'0000.0000.0000.00 00'
'0000.1100.0000.11 00'
'0001.1000.0001.10 00'
'0010.0100.0010.01 00'
'0011.0000.0011.00 00'
'0011.1100.0011.11 00'
'0100.1000.0100.10 00'
'0101.0100.0101.01 00'
'0110.0000.0110.00 00'
'0110.1100.0110.11 00'
'0111.1000.0111.11 00'
'0111.1100.0011.11 00'
'0111.1111.1111.11 01'
'0111.1111.1111.11 01'
'0111.1111.1111.11 01'
WAGO I/O System 750
1)
Hex.
Dec.
0xFCFF
−769
0xFCFF
−769
0xFCFF
−769
0xFE7C
−388
0x0000
0
0x0C0C
3084
0x1818
6168
0x2424
9252
0x3030
12336
0x3C3C
15420
0x4848
18504
0x5454
21588
0x6060
24672
0x6C6C
27756
0x787C
30844
0x7C3C
31804
0x7FFD
32765
0x7FFD
32765
0x7FFD
32765
Status
LED Error
Byte
AI 1, AI 2
Hex.
0x60
On
0x41
On
0x41
On
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x00
Off
0x42
On
0x42
On
0x50
On

Advertisement

Table of Contents
loading