Commissioning
Slot
Module
sequence
1
2
SETTOT_MODETOT_TOTAL
3
SETTOT_MODETOT_TOTAL
4
SETTOT_MODETOT_TOTAL
5
6
DISPLAY_VALUE
7
CONTROL_BLOCK
126
6.7.4
Configuration examples with Simatic S7 HW-Konfig
Example 1
Fig. 66:
Complete configuration using the Promag 53 GSD file (complete device functionality)
It is essential to adhere to the following sequence when configuring the modules in the PROFIBUS
master (Class 1):
Byte length
input data
AI
5
5
5
5
AI
5
-
-
Byte length
Description
output data
Analog Input function block 1
-
Output variable → volume flow
Totalizer function block 1
TOTAL → output variable = volume flow (factory setting)
2
SETTOT → totalizer control
MODETOT → totalizer configuration
Totalizer function block 2
TOTAL → output variable = volume flow (factory setting)
2
SETTOT → totalizer control
MODETOT → totalizer configuration
Totalizer function block 3
TOTAL → output variable = volume flow (factory setting)
2
SETTOT → totalizer control
MODETOT → totalizer configuration
Analog Input function block 2
-
Output variable → mass flow
5
Value for local display
1
Control of device functions
Proline Promag 53 PROFIBUS DP/PA
Endress+Hauser
a0004789