Endress+Hauser PROFI BUS Proline Promag 53 PROFIBUS DP Operating Manual page 54

Electromagnetic flow measuring system
Table of Contents

Advertisement

Wiring
54
a
c
b
Fig. 31:
Connecting the remote version of Promag W/P
a
Connection compartment of wall-mount housing
b
Connection compartment cover of sensor
c
Signal cable
d
Coil current cable
n.c.
Not connected, insulated cable shields
Terminal no.: 6/5 = brown; 7/8 = white; 4 = green; 37 = yellow
a
c
b
DN 40...100
DN 2...25
Fig. 32:
Connecting the remote version of Promag H
a
Connection compartment of wall-mount housing
b
Connection compartment cover of sensor
c
Signal cable
d
Coil current cable
n.c.
Not connected, insulated cable shields
Terminal no.: 6/5 = brown; 7/8 = white; 4 = green; 37 = yellow
Electrode circuit
Meas.signal
Pipe
S1 E1 E2 S2GND E S
6
5
7
8
4
d
n.c.
n.c.
5
7
4
E1 E2 GND E
Electrode circuit
Meas. signal
S1 E1 E2 S2GND E S
6
5
7
8
d
n.c.
n.c.
5
7
E1 E2
GND E
Proline Promag 53 PROFIBUS DP/PA
Coil circuit
EPD
37
36
42
41
n.c.
37
42
41
Coil circuit
Pipe
EPD
4
37
36
42
41
n.c.
4
37
42
41
Endress+Hauser
a0004323-en
a0004321-en

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PROFI BUS Proline Promag 53 PROFIBUS DP and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Profi bus proline promag 53 profibus pa

Table of Contents