Proline Promag 53 PROFIBUS DP/PA
Slot sequence
1
2
3
EMPTY_MODULE
4
EMPTY_MODULE
5
EMPTY_MODULE
6
EMPTY_MODULE
7
CONTROL_BLOCK
Endress+Hauser
Example 2
Fig. 67:
In this example, modules that are not needed are replaced by the module EMPTY_MODULE.
The Promag 53 GSD file is used (manufacturer-specific GSD file, complete device functionality)
With this configuration, the Analog Input function block 1 (slot 1), the totalizer value TOTAL (slot
2) and the cyclic control of device functions CONTROL_BLOCK (slot 7) are activated. The volume
flow is read out cyclically by the measuring device by means of Analog Input function block 1. The
totalizer is configured "without configuration". In other words, in this example it only returns the
totalizer value for the volume flow by means of the TOTAL module and cannot be controlled by the
PROFIBUS master (Class 1).
Byte length
Module
input data
AI
5
TOTAL
5
-
-
-
-
-
Byte length
Description
output data
Analog Input function block 1
-
Output variable → volume flow
Totalizer function block 1
-
TOTAL → output variable = volume flow
-
Empty
-
Empty
-
Empty
-
Empty
1
Control of device functions
Commissioning
a0004790
127