Profibus Dp Connection Diagram - Endress+Hauser PROFI BUS Proline Promag 53 PROFIBUS DP Operating Manual

Electromagnetic flow measuring system
Table of Contents

Advertisement

Wiring
60
4.3.3

PROFIBUS DP connection diagram

Permanent assignment board (order version 53***-***********J)
d
g
b
d
g
b
A (RxD/TxD-N)
27
B (
RxD/TxD-P
)
26
(DGND)
25
(+5 V)
24
23
22
f
21
20
N (L-)
2
L1 (L+)
1
Fig. 34:
Connecting the transmitter, cable cross-section: max. 2.5 mm
A
View A (field housing)
B
View B (stainless steel field housing)
C
View C (wall-mount housing)
a
Connection compartment cover
b
Cable for power supply: 85 to 260 V AC, 20 to 55 V AC,16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
c
Ground terminal for protective conductor
d
Fieldbus cable
Terminal No. 26: B (RxD/TxD-P)
Terminal No. 27: A (RxD/TxD-N)
e
Ground terminal for fieldbus cable shield
Observe the following:
– the shielding and grounding of the fieldbus cable → Page 52
– that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f
Service adapter for connecting service interface FXA 193 (Fieldcheck, ToF Tool - Fieldtool Package)
g
Cable for external termination:
Terminal No. 24: +5 V
Terminal No. 25: DGND
Proline Promag 53 PROFIBUS DP/PA
A
a
B
N (L–)
L1 (L+)
d
e
1 2
g
c
b
b
2
C
a
b
g
d
(+5 V)
(DGND)
B (
RxD/TxD-P
A (RxD/TxD-N)
24 25 26 27
20 21
22 23
c
g
e
d
Endress+Hauser
)
f
a0002308