Error
Error name
code
Synchronous
3042H
operation home
return error
Synchronous
3043H
operation error
Synchronous
operation not
settable
3044H
(In pulser
operation)
Synchronous axis
3045H
difference check
error
Moving amount
3046H
automatic check
value error
Description
- The home return process was
executed with setting the
synchronous operation to "Enabled"
when using the synchronous mode
A.
- A method other than the usable
home return mothods was
executed when using the
synchronous mode B.
The operation was stopped as an
error has occurred on another axis
in the synchronous operaiton.
The setting of the synchronous
opration was changed during the
pulser operation.
The difference between the
movement amounts of the target
axes for the synchronous operation
exceeded the specified difference
threshold.
The difference between the
command value and feedback
value exceeded the moving amount
automatic check value with the
moving amount automatic check
function.
Object
Clear
Simultaneous mode A:
Set the simultaneous operation to
"Disabled" when performing the
home return.
Each axis
A
Simultaneous mode B:
Select a usable home return
method.
Check the unit setting of the
stopped axis.
Each axis
A
If the error occurred repeatedly
with the correct setting values,
please contact us.
Changing the setting of the
synchronous operation should be
Each axis
A
performed when the pulser
operation enabled signal is off.
Check the operation of the target
Each axis
A
axes for the synchronous
operation.
Check the operation of the target
axis.
Each axis
A
Check the parameter for the
moving amount automatic check
function.
Countermeasures
15-7