Ann-S/Pg Serial/Parallel Interface Module - Honeywell Fire-Lite Alarms ES-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-50X:
Table of Contents

Advertisement

Installation
Programming
Following installation and wiring of the ANN-100 LCD annunciator to the FACP, the annunciator must be added to the system via FACP
programming. Refer to the programming section titled "ANN-BUS Setup" on page 87 in this manual for detailed programming information.
Trouble Response
If the ANN-100 is installed but the ANN-BUS is not enabled at the FACP, the ANN-100 will indicate a trouble condition by NOT turning on
its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note
that the FACP will provide no indication of an ANN-100 trouble.
To clear the ANN-100 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-100 at
the FACP.

ANN-S/PG Serial/Parallel Interface Module

Installation
1.
Ensure that all power (AC and DC) has been removed from the FACP.
2.
Connect the ANN-S/PG to the FACP as illustrated in Figure 2.21
3.
Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module.
4.
Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual (refer
to "ANN-BUS Setup" on page 87).
Note that the Auto-configure feature allows the programmer to quickly bring all installed ANN-BUS modules online (refer to "Auto-
Configure" on page 94).
5.
Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 2.21). Only one printer can be connected.
Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6"W x 7-3/4"H x 1-7/16"D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
Connecting a PRN-7 Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire
Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may be
used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-9 cable. One end of the cable will plug into the DB-
9 connector on the PRN-7 printer and the other end plugs into the serial connector on the ANN-S/PG module.
38
ANN-BUS and power wiring are
supervised and power-limited
Primary
24 VDC
ANN-BUS
nonresettable
ES-50X
Figure 2.21 ANN-S/PG Connection to FACP
(-)
Cable Connectors for
(+)
connection to printer
A
B
ANN-S/PG Module
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Optional Module Installation
Parallel
Serial

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-50xc

Table of Contents